Raypak BACnet Interface Module Installation And Operation Manual Download Page 5

BaCnet Interface Module Installation and Configuration Manual

 

5

BaCneT STarTuP Menu SeTuP

-------- SETTINGS ---- 

Season 

Winter

 

System Target 140

o

F

 

<System Settings>

 

<Maintenance>

 

<System Startup>

BACK  

  

 SELECT

-- ARE YOU SURE? -- 

No

 

Yes

BACK  

  

  SAVE

--- BACNET MODE ---

Disable

 

Enable

BACK  

  

  SAVE

- BACNET BAUDRATE -

 

9600

19200

 

38400

BACK  

  

  SAVE

----MS/TP ADDRESS----

1

[            ]

BACK  

  

  SAVE

---- BACNET ID ----

477000

[

           ]

BACK  

  

  SAVE

BaCnet Mode

Enable, Disable  

Default: Disable

Button: 

MENU/<System Startup>/.... Sensor Fault/BACnet Mode

•   This menu option enables or disables the BACnet MSTP capability.  When enabled, 

additional BACnet settings shall be available for further customizing.

--- BACNET MODE ---

Disable

 

Enable

BACK  

  

  SAVE

BaCnet Baud rate

9600, 19200, 38400 

Default: 19200

Button: 

MENU/<System Startup>/.... Sensor Fault/BACnet Mode/BACnet Baudrate

•   For the control to communicate over a BAcnet MS/TP network, it must use the same Baud 

rate as the rest of the network.  The control offers three Baud Rates.

•   If communication was not successful, the baud rate could be the cause.  Check with the 

network administrator for the network baud rate.  Then match it on the control.

- BACNET BAUDRATE -

 

9600

19200

 

38400

BACK  

  

  SAVE

MS/TP address

1 to 127 

Default: 64

Button: 

MENU/<System Startup>/.... /BACnet Mode/BACnet Baudrate/ MSTP 

Address

•   Each device on the MS/TP network must have a unique address.

•   This is the MS/TP address on a RS485 network.  Its MS/TP range is 1 though 127.

•   The MS/TP address must be provided by the Network Administrator.

----MS/TP ADDRESS----

1

[            ]

BACK  

  

  SAVE

BaCnet ID

1 to 4,000,000 

Default: 477,000

Button: 

MENU/<System Startup>/.... / MSTP Address / BACnet ID

•   The BACnet ID is a unique 32 bit number that identifies the control within the BACnet 

network.  No two ID shall be the same even if dealing across networks.

•   It must be provided by the BACnet Network Administrator.

---- BACNET ID ----

477000

[

           ]

BACK  

  

  SAVE

LeD

Yellow LED   Flashes on communication between the BACnet Interface Module 

and the control.

Green LED 

 Flashes on communication between the BACnet Interface Module 

and the BACnet network.

Red LED 

 Flashes steadily to indicate the BACnet Interface Module is 

operational. 

BACnet Interface Module

MSTP

1

2

3

A   GND   B

PRODUCT

COMM

RS485

HT# 

0591

19-00B

Summary of Contents for BACnet Interface Module

Page 1: ...GND B PRODUCT COMM RS485 SYSTEM A B C D 1 2 RUN PROGRAM DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS 3 4 5 6 7 8 9 10 11 12 13 15 14 17 16 18 20 19 21 24 23 29 25 27 26 28 32 30 31 L N T T O O RS 485 mA GND VLT SYS A B C D PWR CUR VLT A mA GND VLT mA GND VLT mA 22 GND VLT mA TEMP OUTDOOR O O TEMP SYSTEM EXTENSION MODULE CUR VLT B CUR VLT C CUR VLT D PROVE DHW SHUTDOWN SETBACK FOR ALL CIRCUITS 120VA...

Page 2: ...ntent 2 Overview 3 Item List 3 Installation 3 Wiring 3 BACnet MS TP Wiring 3 Connecting to Control 4 Connecting to Extension 4 BACnet Startup Menu Setup 5 LED 5 Troubleshooting 6 No LED Light 6 No Communication 6 Specification 6 Wiring to Control and Extension 7 HT 059119 00B ...

Page 3: ...Mount the BACnet Interface Module on a flat surface next to the control The module can be mounted horizontally or vertically Keep the module away from extreme heat cold or humidity Screw the module to the flat surface using the two side tabs with holes No need to remove the BACnet Interface Module cover Wiring No power wiring is required for the BACnet Interface Module It gets its power through th...

Page 4: ...IRE ONLY CAUTION RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de energize the equipment before servicing ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA TSTAT HYBRID RJ45 Communication Cable A Ground B To BACnet MSTP Connecting to Control The BACnet Interface Module communicates all of its information to the control using RJ45 cable the cable is provided with the module Both...

Page 5: ...rate could be the cause Check with the network administrator for the network baud rate Then match it on the control BACNET BAUDRATE 9600 19200 38400 BACK SAVE MS TP Address 1 to 127 Default 64 Button MENU System Startup BACnet Mode BACnet Baudrate MSTP Address Each device on the MS TP network must have a unique address This is the MS TP address on a RS485 network Its MS TP range is 1 though 127 Th...

Page 6: ... and Green LEDs If the Yellow LED is continuously On or Off then check the cable connecting the module to the control If the Green LED is continuously On or Off then check the cable connecting the module to the BACnet network Make sure that the control s Baud Rate and the BACnet Network s are the same See BACnet Baud Rate on page 5 Specification Control Communication RJ45 to control Cable is provi...

Page 7: ... switch may be required to de energize the equipment before servicing ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA TSTAT HYBRID RJ45 Communication Cable RJ45 Cable Extension RJ11 Extension Cable F H J Power CAUTION Risk of Electric Shock More than one disconnect switch may be required to de energize the equipment before servicing PWR L N 1 2 E 3 4 F 5 6 G 7 8 H 9 10 I 11 12 EXTENSION MODULE RS 485 Ex...

Page 8: ...HT 059119 00B Raypak Inc 2151 Eastman Ave Oxnard CA 93030 PH 805 278 5300 FAX 805 278 5468 ...