29
PIPE SIZING AND PUMP SELECTION
The pipe sizing for water heating and mechanical heating systems should be carried out by persons
competent to do so, choosing the most suitable pipe size for each individual application. Reference to
the technical specifications of the water heater and local regulatory authority requirements must be
made.
PUMP SELECTION APPLICATIONS
UP TO 65
o
C
on page 29 provides minimum pipe and pump sizes for typical water heating installations up to
65
o
C at the optimum temperature rise for these applications (20
o
K).
PUMP SELECTION APPLICATIONS ABOVE 65
o
C
In mechanical heating applications, the MVB is designed to operate on a primary flow and return
circuit serving the main system flow and return circuit.
on page 39 provides minimum pipe
and pump sizes for primary circuit in mechanical heating and domestic hot water applications over
65
o
C at the optimum temperature rise for these applications (15
o
K).
MVB Pipe Size and Pump and Pipe Selection Chart
–
DHW and Hydronic Applications up to 65
o
C
(20 degree rise)
MVB
Model
Pump
Model
Branch
Size
mm
Minimum Manifold Header Size (mm) / Pump Speed Setting
1 Unit
2 Units
3 Units
4 Units
pipe
dia
speed
pipe
dia
speed
pipe
dia
speed
pipe
dia
speed
mm
mm
mm
mm
910500
UPS32-80N
50
50
3
65
3
80
3
100
3
910750
UPS32-80N
65
65
3
80
3
100
3
100
3
911000
Magna 1 40-120
65
65
PP1
100
PP1
100
CP1
125
PP1
911250
Magna 1 40-120
80
80
CC2
100
CC2
125
CC2
125
CC3
911500
Magna 1 40-120
80
80
CC3
100
CC3
125
CC3
150
CC3
911750
Magna 1 65-150
100
100
CC2
125
CC2
150
CC2
200
CC2
912000
Magna 1 65-150
100
100
PP2
125
PP2
150
PP2
200
PP2
Note: Manifold header sizes are minimum requirements for water heater performance.
Pipe and pump sizing is for primary circuits in DHW and hydronic applications up to 71
o
C for a 20
degree rise.
Header sizing is based on a total length of 20m of primary flow and return piping and 20 bends,
excluding equa-flow manifolds on storage tanks and MVBs, at 1.2m/sec velocity in copper pipe.
Magna 1 pumps have 3 speed control modes. PP = Proportional Pressure, CP = Constant Pressure, CC =
Constant Curve. UPS pumps have 3 fixed speed control settings. The appropriate speed setting must be
used to ensure correct operation
Table 9: Pump and Pipe Sizing for Water Heating Applications up to 65
o
C