Raypak 5300 Owner'S Manual Download Page 8

5

V. System Start-Up

1. Verify that the 

Power 

lamp is ON and that the pool/spa pump is running and circulating 

properly.

2. Verify that the control panel 

Spa-Remote-Pool

 

switch is in the 

Remote

 (OFF) position; see 

the figure.

3. Turn the control switch to either 

Pool

 or 

Spa

 to turn the system ON and raise the thermostat 

setting above the current water temperature. At this time the 2 green lamps should illuminate. 
The fan and compressor should start up and run simultaneously.

NOTE: The heat pump will not run when the Remote 
position is selected on the Pool/Spa selector switch and 
there is no remote control system attached.

4.Allow the heat pump to operate for a few minutes to 
stabilize operating pressures and to allow various 
component temperatures to normalize. 

5. Verify that the discharge air temperature is 
approximately 8° - 10° cooler than the air entering the 
unit. If not, see Troubleshooting, Section XI.

VI. Seasonal Start-Up or Annual Check

NOTE: At the beginning of the heating season, or whenever the pool water temper- 
ature is to be raised several degrees, the pool pump and heat pump may need to 
operate continuously for several days. During summer months, only a few hours 
per day may be necessary, or none at all.

1. Remove leaves, pine needles, etc. from the evaporator coil. Clean the coil by gently applying 

a mild solution of household liquid soap and water.

2. Gently rinse the coil with water; do NOT use high pressure.

3. Backwash or otherwise clean the pool filter. If necessary, clean the skimmer basket and pump 

strainer.

4. Replace the front and back caps; see the Series Hookup Diagram on the last page of this 

manual for cap location.

5. Set the valves

 

to assure proper water flow through the unit.

NOTE: If the pool pump and heat pump shut OFF before the water temperature is 
raised to the desired level, you must lengthen the running time of both. To do this, 
reset the time clock dial for the longer running time, or manually operate the pump 
with the timer override switch. Since the heat pump capacity and efficiency are both 
greater at higher ambient air temperatures, run time should be set to take 
advantage of all daylight hours, when the air is generally warmer.

Spa thermostat

Pool/Spa selector

Pool thermostat

 switch

CAUTION

To clean the fins, spray gently with a garden hose.

pressure wash, which will bend the fins and can void the warranty.

  DO NOT

Summary of Contents for 5300

Page 1: ...d in U S A Part No 00 02107A 5300 8300 6300 Models The instructions in this manual are for the use of qualified individuals specially trained and experienced in the installation and maintenance of this type of equipment and related system components Installation and service personnel are required by some states to be licensed Persons not qualified shall not attempt to install service or maintain t...

Page 2: ... could void the heat pump warranty ALWAYS follow the product manufacturer s directions when adding any chemicals to your pool AUDIENCE The audience for this manual is twofold 1 For the installing contractor to provide information for the proper installation and adjustment of the heat pump 2 For the owner operator to explain the features operation safety precautions and service maintenance of the h...

Page 3: ...ons 1 II Electrical Connections 2 III Water Connections 3 IV Controls and Indicator Lamps 3 V System Start Up 5 VI Seasonal Start Up or Annual Check 5 VII Heat Pump Running Time 6 VIII Summer Shutdown 6 IX Freeze Protection 6 X Maintenance 7 XI Troubleshooting 7 XII Service Call Verification 9 Plumbing Diagrams 10 ...

Page 4: ...be required to operate longer to accomplish the desired results It may at certain times operate as much as 24 hours per day However this should not be of concern to the owner because the unit is designed to operate continuously Even though it may operate continuously for many hours it will still heat the pool with greater economy than other types of fossil fuel heaters Place a cover or blanket ove...

Page 5: ...alled in areas where freezing temperatures can be encountered drain the water circuit to prevent possible freeze up damage See Section IX Freeze Protection II Electrical Connections The table below lists the typical electrical power requirements for your heat pump Refer to the unit rating plate below the control panel for precise power requirement for your unit and for ampacity and over current pr...

Page 6: ...ER the heat pump Improper installation of erosion type automatic chemical feeders can result in serious damage to or premature failure of the heat pump and will void the heat pump warranty IV Controls and Indicator Lamps Your heat pump incorporates safety controls and indicators to ensure its safe reliable operation Water Pressure Switch Prevents operation when the pump is OFF The unit requires 5 ...

Page 7: ...n lit indicates normal water flow Heat Demand green lamp When lit indicates the actual water temperature is below the target water temperature Compressor Delay Active amber lamp Under normal operation when lit indicates compressor anti short cycle timer is active The fan will run but the compressor will be OFF for 6 to 8 minutes Defrost Active red lamp When lit indicates unit is in defrost mode De...

Page 8: ...d heat pump may need to operate continuously for several days During summer months only a few hours per day may be necessary or none at all 1 Remove leaves pine needles etc from the evaporator coil Clean the coil by gently applying a mild solution of household liquid soap and water 2 Gently rinse the coil with water do NOT use high pressure 3 Backwash or otherwise clean the pool filter If necessar...

Page 9: ...OFF 2 Turn the heat pump circuit breaker or disconnect switch to OFF 3 Leave the valves set the way they are unless additional circulation is required DO NOT stop all flow through the heat pump 4 IMPORTANT Remember to reset the valves before the next heating season or the heat pump will not operate properly IX Freeze Protection If the heat pump is installed in a location subject to freezing condit...

Page 10: ...holes in the base of the unit are not plugged with dirt or debris 2 If condensation becomes a problem optional drain pans are available from your heat pump distributor or pool dealer XI Troubleshooting If your heat pump does not operate or simply does not heat your pool water the indicator lamps on the front control panel see Section IV can provide valuable clues as to what is wrong and may even i...

Page 11: ...ight compared to 4 degrees or fewer when a blanket is used Without a blanket the total heat gained during the day can be lost overnight Are rapid heat losses occurring in some other way such as high wind spillage rainfall flow through solar panels at nights or a high water table B UNIT IS NOT RUNNING Is the control panel Power lamp ON If not the circuit breaker may be shut OFF or tripped Reset the...

Page 12: ...er flow or time clock adjustment NOTE The MANUFACTURER IS NOT RESPONSIBLE for these adjustments POWER SUPPLY Verify that all circuit breakers are reset and working properly If the Power lamp on the control panel still does not light contact the installing dealer since it may be a power problem requiring an electrician WATER FLOW Verify that the pool filter is clean to provide good flow Verify that...

Page 13: ...nections are 2 inch unions Plumb the heat pump after the filter and before any chlorinators Water In from pool or spa Water Out to pool or spa Filter For systems with pumps of less than 2 HP under 80 gpm no external bypass is required Connections are 2 inch unions Plumb the heat pump after the filter and before any chlorinators Water In from pool or spa Water Out to pool or spa Filter ...

Reviews: