START-UP PROCEDURE

Run full system flow for two minutes.

Initiate PID pump control to achieve target inlet
temperature by slowing injector pump.

Boiler ΔT will not increase during bypass operation.

If target temperature is not achieved after seven
minutes from “call for heat”, the system will shut
down. 

Sequence of Operation

1) Supply separate 220VAC, 1 Ø, 60 Hz power to

Cold Run control.

2) Call for heat occurs at heater.
3) TRIG terminal of Economaster connection on

heater CPW board outputs 24VAC to terminal 4 of
terminal block 3 located in Cold Run controller.

4) Terminal 4 of TB 3 sends 24VAC to the coil of the

SPST relay located in the cold run control panel.

5) The SPST relay coil is energized and closes the

contacts allowing 24VAC from the Cold Run con-
trol transformer to be sent to the CFH terminal of
the Cold Run circuit board.

a) A two second delay occurs from the CFH signal

waiting to send power from terminal MC of the cold
run circuit board. 

6) J9 terminal on the heater CPW board (interlock

connection) outputs a 24 VAC signal to terminal 2
of terminal block 3 located in the cold run con-
troller.

7) 24 VAC is sent from terminal 2 of terminal block 3

to the NO contacts of the DPST relay located in

the cold run control panel.

8) After the two second delay on the cold run circuit

board, pin MC outputs a 24 VAC signal to terminal
AL0 of the Hitachi inverter.

9) The AL0 relay closes and outputs a 24 VAC signal

to the coil of the DPST relay located in the cold run
control panel.

10) The DPST relay coil energizes and closes the NO

contacts.

11) Once the NO contacts of the DPST close, the

heater 24 VAC is sent back to the heater to com-
plete the Economaster circuit (pin 3 of terminal
block 3) and the interlock circuit (pin 1 of terminal
block 3) allowing the heater to fire.

12) Pin SC of the cold run circuit board sends 24VAC

to Pin 1 (Forward) on Hitachi Inverter.

13) PCS terminal on Inverter outputs 12VDC signal to

the common terminal of the reset switch located
on the bottom of the cold run control panel.

14) The 12VDC signal crosses over the reset switch

and goes to Pin FS on cold run circuit board.

15) 12VDC on pin FS is jumpered to pin S1 on the

cold run circuit board.

16) Pin FR on the TVC board outputs 10VDC to the

Inverter to drive injector pump at full speed two-
minutes waiting for the heater to reach full fire.

17) After the two-minute delay the 10VDC output sig-

nal from pin FR reduces to approximately 8VDC at
the inverter thus slowing the pump to approxi-
mately 50 Hz.

18) The output signal continues to vary depending on

the heater inlet temperature.

The heater will lockout and shut down if the set point
on the inlet temperature is not achieved within seven-
minutes from a call for heat.

The DIP switches on the Hitachi Inverter must be set
as indicated on Fig. 19 below.

Fig. 18: Control Board

Fig. 19: DIP Switch Settings

Summary of Contents for 241275

Page 1: ...nd kept adjacent to the heater or in another safe place for future reference Catalog No 1000 57A Effective 02 28 07 Replaces 02 24 06 P N 241275 Rev 2 INSTALLATION AND OPERATING INSTRUCTIONS COLD WATE...

Page 2: ...2...

Page 3: ...tream and read the thermometer 3 NOTE When this water heater is supplying general purpose hot water for use by individuals a thermo statically controlled mixing valve for reducing point of use water t...

Page 4: ...e sensor A tem plate is supplied for field installed kits to locate the control box properly Attaching the Temperature Sensor Avoid routing wiring on or near other electrical wires conduit motors spar...

Page 5: ...minates GREEN 2 START UP MODE LED on PCB illuminates YEL LOW Before 7 minutes it should go out if boiler inlet temperature is approaching the set point tem perature 3 The ACTUATOR should be in the ful...

Page 6: ...erminal 2 of terminal block 3 to the NO contacts of the DPST relay located in the cold start control panel 14 After the two second delay on the cold start circuit board pin MC outputs a 24 VAC signal...

Page 7: ...ater IF VALVE DOES NOT MOVE Check for voltage out at TB2 1 Should be a 1VDC to 10VDC output to the actuator valve If no voltage is present check for volt age at TB2 3 there should be a 12VDC signal If...

Page 8: ...8 Cold Water Start Troubleshooting Guide...

Page 9: ...9 Wiring Diagram...

Page 10: ...ode ANSI NFPA 70 For Canada only CAN CGA B149 1 installation Code B149 1 and CSA C22 1 C E C Part 1 and Part 2 Mounting the Control Box The control box should be mounted on the side of the heater to w...

Page 11: ...1532 120 22 12 4 62 42 1911 1 3hp 1632 5 6 1802 120 25 13 68 45 1911 1 3hp 1632 5 6 2002 132 26 19 74 46 1935 3 4hp 1634 6 1 2072 132 27 19 75 47 1935 3 4hp 1634 6 1 2342 132 30 21 4 80 50 1935 3 4hp...

Page 12: ...the system 4 Allow heater to cool down before attempting work In order to install the pump cover you will need to rotate the pump body so that the electrical box is point ing downward as outlined in t...

Page 13: ...olts secur ing the pump body in place 4 You will now be able to install the pump cover See Fig 18 and 19 Fig 15 Reposition the pump body so that the electrical box points downward Fig 16 Place the cov...

Page 14: ...14 Typical Boiler Piping Hi Delta shown...

Page 15: ...signal to terminal AL0 of the Hitachi inverter 9 The AL0 relay closes and outputs a 24 VAC signal to the coil of the DPST relay located in the cold run control panel 10 The DPST relay coil energizes a...

Page 16: ...16 Wiring Diagram...

Page 17: ...ornia 1 800 627 2975 Inside California NO Verify 120VAC from TB1 on the heater and correct YES Does TB1 of cold run controller have 120 VAC Heater is in standby mode Correct Wiring YES NO NO YES YES N...

Page 18: ...18 ILLUSTRATED PARTS LISTS Cold Water Start...

Page 19: ...A 007353F PUMP WATER BR 2 1 2 FLANGE 3 4 HP 007348F 007348F PUMP WATER CI 2 1 2 FLANGE 3 4 HP 007354F 007354F PUMP WATER BR 2 1 2 FLANGE 1 HP 007348F 007348F PUMP WATER CI 2 1 2 FLANGE 1 HP 007354F 00...

Page 20: ...20 Cold Water Run...

Page 21: ...2 7 0 0 P H 4 1 E G N A L F 2 I C R E T A W P M U P PUMP WATER BR 2 1 2 FLANGE 3 4 HP 007348F 007348F PUMP WATER CI 2 1 2 FLANGE 3 4 HP 007354F 007354F F 1 5 3 7 0 0 F 1 5 3 7 0 0 P H 1 E G N A L F 2...

Page 22: ...raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Raypak Canada Limited 2805 Slough St Mississauga Ontario Canada L4T 1G2 905 677 7999 Fax 905 677 8036 Litho in U...

Reviews: