background image

Catalog No.:  3500.24B 

Effective:  1-15-08 

Replaces:  7-15-04

 

Raytherm - Type WH 

 

 

Models 2100-4100 

Model 

           

 

 

 

MODELS WH 2100 – 4001

MBTUH Width 

Overall 

Height 

Gas 

Conn. 

Water 
Conn. 

Flue  

Dia. 

Model 

No. 

Input Output 

Approx. 

Shipping 

Weight (lbs) 

WH-2100 2100  1722 

61 

68-1/4 

24 

1400 

WH-2500 2499  2049 

70 

68-1/4 

26 

1580 

WH-3001 3000  2460  81-1/4  68-1/4 

28 

1750 

WH-3500 3500  2870  92-1/2  68-1/4 

30 

1920 

WH-4001 4000  3280 103-3/4 68-1/4 

32 

2100 

*  1-1/2” or 2”, contingent on water heater type code requirements 

NOTES:  Dimensions are in inches. 

Ratings are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 
4% for every 1,000 feet above sea level. 

 

HEATER RATES OF FLOW AND PRESSURE DROPS

 

20°F 

T 30°F 

T 40°F 

T

 

Model 

No. 

GPM 

P (ft)  GPM 

P (ft)  GPM 

P (ft)

WH-2100 172  11.0  115  4.9  N/A  N/A 
WH-2500 

N/A N/A 137  7.5  102  4.3 

WH-3001 

N/A N/A 164 11.2 123  6.5 

WH-3500 

N/A N/A 191 16.8 144  9.3 

WH-4001 N/A  N/A  N/A N/A 164 12.8 

Maximum acceptable flow through heat exchanger tubes is 
200 GPM. 

HEATER RECOVERY RATES (GPH)

 

Temperature Rise 

Model 

No. 

20°F 30°F 40°F 50°F 60°F 80°F 100°F

WH-2100

10336

6890 5168 4134 3445 2584 2067 

WH-2500

12300

8200 6150 4920 4100 3075 2460 

WH-3001

14765

9844 7383 5906 4922 3691 2953 

WH-3500

17227

11484

8613 6891 5742 4301 3445 

WH-4001

19688

13125

9844 7875 6563 4922 3938 

 

Raypak, Inc.  

ƒ

  2151 Eastman Avenue, Oxnard, CA  93030  

ƒ

  (805) 278-5300  

ƒ

  Fax (800) 872-9725  

ƒ

  www.raypak.com 

Reviews: