Catalog No.: 2000.26M
Effective: 12-1-07
Replaces: 12-1-99
Raytherm - Type H
Hydronic Heating Boilers
Model
MODELS H 2100 THRU 4001
MBTUH
Dimensions
(inches)
Approx.
Model Natural
Gas Width
Overall
Height
Gas Conn.
Water Conn.
Flue Dia.
Shipping
No. Input
Output A
B
G
H
K Weight
(Lbs.)
H-2100 2100 1722 61.0
68-1/4
*
3**
24
1400
H-2500 2499 2049 70.0
68-1/4
*
3**
26
1580
H-3001 3000 2460 81-1/4 68-1/4
2
3**
28
1750
H-3500 3500 2870 92-1/2 68-1/4
2
3**
30
1920
H-4001 4000 3280 103-3/4 68-1/4
2
3**
32
2100
* 1-1/2” or 2” contingent on boiler type code requirements
NOTE: Ratings are for elevations up to 2,000 feet. For
elevations over 2,000 feet, reduce ratings 4% for
every 1,000 feet above sea level.
** 4” on one-pass option
BOILER RATE OF FLOW AND PRESSURE DROP
Model 10°
∆
T 20°
∆
T
30°
∆
T
40°
∆
T
No.
GPM
∆
P FT
GPM
∆
P FT
GPM
∆
P FT
GPM
∆
P FT
H-2100 N/A N/A 172 11.0 115 5.0 N/A N/A
H-2500 N/A N/A N/A N/A 137 7.5 102 4.3
TWO-PASS H-3001 N/A
N/A
N/A N/A 164 11.2 123 6.5
H-3500 N/A N/A N/A N/A 191 16.2 144 9.3
H-4001 N/A N/A N/A N/A N/A N/A 164 12.8
H-2100
344
14.0
N/A
N/A N/A N/A N/A N/A
H-2500 N/A N/A 205 5.3 N/A N/A N/A N/A
ONE-PASS H-3001 N/A
N/A
246 7.8 N/A N/A N/A N/A
H-3500 N/A N/A 287 11.0 191 5.0 N/A N/A
H-4001 N/A N/A 328 14.8 219 6.8 N/A N/A
N/A – Not Applicable
NOTES:
Values represent maximum flows and pressure drops for closed heating systems.
Maximum acceptable flow through heat exchanger tubes is 200 GPM (two-pass); 400 GPM (one-pass)
Single-pass heat exchangers are to be used only when flow rates exceed the allowable for two-pass