background image

Catalog No.:  2000.203E 

Effective:  12-1-07 

Replaces:  4-1-05

 

Raytherm - Type H   

 

Hydronic Heating Boilers - Indoor 

Model 

           

 

 

 

 
 
 

 

 

 

 

 

 

 

 

Dimensions (Inches) 

Shipping Weight  

(Lbs.) – Approx. 

Model 

No. 

MBTU 

Input 

MBTU 

Output 

AFUE 

 (%) 

Width 

Height 

 

Flue Dia. 

No Pump

 

w/ Pump

H-181* 181  148  82.6 18-1/4 62-5/8 12-1/16 

191 

221 

H-261 264  216  82.7 22-3/8 

62-7/8 11-1/8 

214 

244 

H-331 

334 274 N/A 

25-3/4 

63-3/4 10-3/4 

234 

264 

H-401* 

399 327 N/A 

29-1/4 65-3/8 12-1/2 

253 

283 

*  Exceptions on H3 (two-stage-fired) models: 

-

  Model H3-181 has an 18-1/4” gas connection 

-

  Model H3-401 has 375 MBTU Input and 308 MBTU Output 

NOTE: Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000, reduce ratings at the rate of 4% for each  

1,000 feet above sea level. 

 

BOILER RATE OF FLOW AND PRESSURE DROP

 

10° 

T

 

20° 

T

 

30° 

T

 

Model 

No. 

GPM 

P FT 

GPM 

P FT 

GPM 

P FT

H-181  30  4.2  N/A N/A N/A N/A 
H-261 43 8.5 22 2.2 N/A N/A 
H-331 N/A N/A  27  3.4  N/A N/A 

H-401 

N/A N/A 33 5.2 22 2.3 

N/A – Not Applicable 
 

 

 

 

Low NOx

Raypak, Inc.  

ƒ

  2151 Eastman Avenue, Oxnard, CA  93030  

ƒ

  (805) 278-5300  

ƒ

  Fax (800) 872-9725  

ƒ

  www.raypak.com 