Rayleigh Instruments RI-F200 Instruction Manual Download Page 1

RI

-

F200

-

IM

-

V01

 

 

1

 

 

 

RI

-

F200

-

B

-

MB / RI

-

F200

-

G

-

MB

 

 

RI

-

F200

-

B

-

C / RI

-

F200

-

G

-

C

 

 

RI

-

F200   

Instruc on Manual

 

 

                                             

X 4    

 

 

 

                         

 

RTU

 

Pulse SO

 

Safety related no fica on, symbols and instruc ons that appear in this 

opera ng manual or on the equipment must be strictly followed to 

ensure the safety of personnel as well as the instrument. If the      

equipment is not used in a manner specified by the manufacturer it may 

impair the protec on provided by the equipment

 

· 

Do not use the equipment if there are mechanical damage

 

· 

Do not exceed the stated maximum ra ngs of the device

 

· 

No repairs, maintenance or adjustments are possible

 

· 

Read the complete instruc on manual prior to installa on or       

opera ng the unit

 

· 

The equipment in its installed state must not come into close      

proximity to any hea ng sources, oils, steam, caus c vapours or  

other unwanted process by

-

products

 

· 

Do not use in hazardous or classified loca on where explosion or 

other dangers can be triggered by the device

 

PRODUCT SAFETY

 

INSTALLATION PRECAUTIONS

 

Risk of electric shock!

 

Only to be installed by a competent person

 

 

· 

To prevent the risk of electrocu on, always isolate and lock

-

off the 

power supply to the equipment prior to undertaking any work

 

· 

Always confirm absence of electricity prior to star ng work using           

appropriate voltage detec on equipment

 

· 

Wiring shall be done strictly according to the terminal layout

 

· 

Confirm that all connec ons are correct before energizing the   

equipment

 

· 

Rou ng of cables shall be way from any internal EMI source

 

· 

Copper cable should be used

 

· 

All wiring to be in accordance with applicable local standards

 

Specifica ons

 

Accuracy

 

Wiring Input

 

3Ø 4 wire, 3Ø 3 wire, 2Ø 3 wire, 1Ø 2 wire

 

Voltage V L

-

N and V L

-

L

 

±0.5% of full scale

 

Rated Input Voltage

 

3x 11...300V AC (L

-

N), 19...519V AC (L

-

L)

 

Current

 

±0.5% of full scale

 

Frequency Range

 

45...65Hz

 

Frequency for L

-

N > 20V, L

-

L > 35V

 

±0.1% of full scale

 

CT Primary

 

1A/5A...10,000A configurable

 

Ac ve, Reac ve and Apparent Power

 

1%

 

CT Secondary

 

1A or 5A (max ra ng x1.2)

 

Power Factor

 

±0.01 of Unity

 

VT Primary

 

100...500kV configurable

 

Ac ve Energy

 

Class 1 (IEC/EN 62053

-

21)

 

VT Secondary

 

100...500V AC (L

-

L) configurable

 

Reac ve Energy

 

Class 2 (IEC/EN 62053

-

23)

 

Auxiliary / Power consump on

 

100...240V AC (±15%)   45...65Hz  /  < 8VA

 

Display Update Rate

 

1 sec all parameters

 

Opera ng / Storage Temperature

 

-

10…55°C   /   

-

20…70°C

 

Wh Resolu on and Default Pulse Weight 

 

Humidity

 

0...85% non

-

condensing

 

 
 

 

 
 

Example

 

If CT = 100/5A (CT ra o = 20) & VT = 350/350V (VT Ra o = 1)

 

Wh resolu on = 0.1kWh (20 x 1 = <150) | Pulse O/P default = 0.1kWh/pulse

 

Protec on Degree (IEC/EN60529)

 

IP54 Front only (rubber gasket fi ed)

 

Pulse Output

 

External 5...27V DC / 100mA max

 

Pulse Resolu on / Dura on

 

0.01...99.99kWh per imp / 0.1...2 sec

 

Communica on

 

Modbus RTU over RS485

 

MBus (EN13757)

 

 

CT Ra o x VT Ra o

 

<15

 

<150

 

<1500

 

<15k

 

<150k

 

Wh / VArh / VAh

 

0.01k

 

0.1k

 

1k

 

0.01M

 

0.1M

 

>150k

 

1M

 

INT

 

0.01k

 

0.1k

 

1k

 

0.01M

 

0.1M

 

0.1M

 

MECHANICAL INSTALLATION

 

EO&E: Document subject to change

 

Installa on & Environmental

 

Panel mounted, indoor used only.

 

Installa on category: 

III 

(300V L

-

N)

 

Al tude: up to 2000 m

 

Protec on Class: 

II

 

Pollu on degree: 

II

 

 

All terminal covers must be fi ed a er wiring

 

Summary of Contents for RI-F200

Page 1: ...Rou ng of cables shall be way from any internal EMI source Copper cable should be used All wiring to be in accordance with applicable local standards Specifica ons Accuracy Wiring Input 3Ø 4 wire 3Ø 3 wire 2Ø 3 wire 1Ø 2 wire Voltage V L N and V L L 0 5 of full scale Rated Input Voltage 3x 11 300V AC L N 19 519V AC L L Current 0 5 of full scale Frequency Range 45 65Hz Frequency for L N 20V L L 35V ...

Page 2: ...ology below 500m Max 32 meters Fuse class CC UL fast ac ng 600V Ra ng 0 5A For Volt free PLC or digital input voltage must be provided by the addi on of a DC PSU Single Core 0 5 4mm2 Ø 2 5mm max Stranded 0 5 2 5mm2 7mm Ø 2 5 mm 0 8 Nm Max 3P4W 3 CTs 1P2W 1 CT 2P3W 2 CTs 2 VTs 2P3W 2 CTs 3P3W 2 CTs 2 VTs 3P3W 2 CTs 3P4W 3 CTs 3 VTs Voltage and current must be from same phase ...

Page 3: ...30 ü 14 14 Demand interval length 1 1 30 min ü 15 15 Max Auto Display Pages 21 1 21 ü 16 16 Change Page Sequence 1 21 No YES 1 21 ü 17 17 Pulse Weight 0 01 00 01 99 99 kWh imp ü 18 18 Pulse Dura on 0 1 0 1 2 0 Sec ü X 19 MBus Secondary ID Serial 0000 0000 9999 9999 ü 19 20 Factory Default No No Yes Does not reset energy demand values ü 20 21 Reset Energy No No Yes Password 1 ü Once entered reset e...

Page 4: ... www rayleigh com E sales rayleigh com Rayleigh Instruments Limited SP Z o o European Office Ul Aleje Jerozolimskie 214 Warsaw Poland 02 486 W www rayleigh pl E sales rayleigh pl E x1 9 Ac ve Energy kWh L1 IP L2 IP L3 IP L1 EP L2 EP L3 EP IP EP Net IP EP x10 18 Reac ve Energy kVArh L1 IP L2 IP L3 IP L1 EP L2 EP L3 EP IP EP Net IP EP x19 22 Apparent Energy kVAh L1 L2 L3 Hold 10 sec change Page Scroll...

Reviews: