Sheilds Ensviromental Services RI-D384-C ( Page 2 of 4 )DM-V1.10-Rayleigh Instruments 13-04-16
ONLINE PAGE DESCRIPTION
There are 2 dedicated keys labelled as PAGE and PRG with symbols
and to read meter parameters.
At power on the meter displays average phase to neutral voltage and
active energy of three phases. If any key is not pressed for 60
seconds the unit resumes manual mode.
KEY
PRESS
PARAMETER
KEY
DESCRIPTION
ONLINE PAGE DESCRIPTION FOR 3P4W and 3P3W
Press
page
( ) key
(1st time)
——
Displays line to neutral
voltage of three phases
Press ( ) key
Displays line to line voltage
of three phases (
)
Press
page
( ) key
(2nd time)
——
Displays phase current of three phases
(
)
Press
page
( ) key
(
3rd time
)
——
Displays average phase to neutral
voltage, current and power factor of
three phases and frequency
Press ( ) key
Displays average line to line voltage,
current and power factor of three phases
and frequency (
)
Press
page
( ) key
(4th time)
——
Displays power factor of three phases
and frequency
Press ( ) key
1st time
Displays active power of three phases
Press ( ) key
2nd time
Displays reactive power of three phases
Press ( ) key
3rd time
Displays apparent power of three
phases
Press ( ) key
4th time
Displays total active power of three
phases (
)
Press ( ) key
5th time
Displays total reactive power of three
phases (
)
Press ( ) key
6th time
Displays total apparent power of three
phases (
)
Press ( ) key
7th time
Displays Max (2
nd
row) and Min (3
rd
row)
demand of total active power (
)
Press ( ) key
8th time
Displays Max (2
nd
row) and Min (3
rd
row)
demand of total reactive power (
)
Press ( ) key
9th time
Displays Max demand of total apparent
power (
)
SERIAL NUMBER DESCRIPTION
Press ( ) key for 10 seconds to 8 digit serial number only for 10
seconds on the 2nd and 3rd lines of the display
CONFIGURATION
There are 3 dedicated keys with symbols marked as
, and use these 3 keys to enter into configuration menu or
to change the settings.
Note :
The settings should be done by a professional, after
going through this users manual and after having understood the
application situation.
For the configuration setting mode:
● Use and keys for 3 seconds to enter or exit from the
configuration menu.
● Use shift key to move curser left or right by one digit each time.
After last digit of display cursor shifts to 1st digit of display.
● Use increment key for increasing the parameter value.
● Use key to save the setting and move on to the next page.
● Use and keys to go back to the previous page.
Config
Page
Function
Range or
Selection
Factory
Setting
Password
0000-9999
1000
1.0
Change Password
No/Yes
No
1.1
New Password
0000-9998
1000
2.0
Network Selection
3P4W
3P3W
1P2W-P1
1P2W-P2
1P2W-P3
3P4W
3.0
CT Secondary
1-5A
5A
4.0
CT Primary
5A - 10000A
5A
5.0
PT Secondary
100 - 500V
350V
6.0
PT Primary
100-500KV
350V
7.0
Slave ID (Address)
1-255
1
8.0
Baud Rate
300, 600, 1200,
4800, 9600 &
19200
9600
9.0
Parity
None, Even, Odd
None
10.0
Stop Bit
1 or 2
1
11.0
Back Light
0-7200S
0000
12.0
Demand Interval Method
Sliding/Fixed
Sliding
13.0
Demand Interval Duration
1-30
15
14.0
Demand Interval Length
1-30min
1
15.0
Max auto Pages
1 to 18
18
16.0
Change Page Sequence
No/Yes
No
16.1
Page Sequence 1
No/Yes
No
16.2
Page Sequence 2
No/Yes
No
16.3
Page Sequence 3
No/Yes
No
16.4
Page Sequence 4
No/Yes
No
16.5
Page Sequence 5
No/Yes
No
16.6
Page Sequence 6
No/Yes
No
16.7
Page Sequence 7
No/Yes
No
16.8
Page Sequence 8
No/Yes
No
16.9
Page Sequence 9
No/Yes
No
16.10
Page Sequence 10
No/Yes
No
16.11
Page Sequence 11
No/Yes
No
16.12
Page Sequence 12
No/Yes
No
16.13
Page Sequence 13
No/Yes
No
16.14
Page Sequence 14
No/Yes
No
16.15
Page Sequence 15
No/Yes
No
16.16
Page Sequence 16
No/Yes
No
16.17
Page Sequence 17
No/Yes
No
16.18
Page Sequence 18
No/Yes
No
17
Reset Factory Default
No/Yes
No
18
* Password
0001-9999
1001
Press
page
( ) key
(1st time)
——-
Displays average voltage line to neutral
(1
st
row), import active energy (2
nd
row)
and export active energy (3
rd
row) of
three phases (
)
Press ( ) key
Displays average voltage line to neutral
(1
st
row), import reactive energy (2
nd
row) and export reactive energy (3
rd
row)
of three phases (
)
Press ( ) key
3 seconds
Displays average voltage line to neutral
(1
st
row) and apparent energy (3
rd
row)
of three phases (
)
For this key function in 1st row for 3P3W voltage will be
average line to line.
Note:
For 3Phase 3Wire network only
(
) marked page will be displayed.
KEY
PRESS
PARAMETER
KEY
DESCRIPTION
ONLINE PAGE DESCRIPTION FOR 1P2W-P1/P2/P3
Press
page
( ) key
(1st time)
——
Displays line to neutral
voltage of selected phase
Press
page
( ) key
(2nd time)
——
Displays phase current of selected
phase
Press
page
( ) key
(4th time)
——
Displays power factor of selected
phase and frequency
Press ( ) key
1st time
Displays active power of selected
phase
Press ( ) key
2nd time
Displays reactive power of selected
phase
Press ( ) key
3rd time
Displays apparent power of selected
phase
Press ( ) key
4th time
Displays MAX (2
nd
row) and MIN (3
rd
row) demand of total active power
Press ( ) key
5th time
Displays MAX (2
nd
row) and MIN (3
rd
row) demand of total reactive power
Press ( ) key
6th time
Displays total MAX demand of total
apparent power
Press
page
( ) key
(5th time)
——
Displays average voltage line to
neutral (1
st
row), import active energy
(2
nd
row) and export active energy
(3
rd
row) of selected phase
Press ( ) key
1st time
Displays average voltage line to
neutral (1
st
row), import reactive
energy (2
nd
row) and export reactive
energy (3
rd
row) of selected phase
Press ( ) key
2nd time
Displays average voltage line to
neutral (1st row) and apparent
energy (3rd row) of selected phase
Note:
For 1Phase 2Wire network, only selected phase parame-
ter will be displayed
Config
Page
Function
Range or
Selection
Factory
Setting
18.01
Reset Active Energy
No/Yes
No
18.02
Reset Reactive Energy
No/Yes
No
18.03
Reset Apparent Energy
No/Yes
No
18.04
Reset Max Power
No/Yes
No
* For resetting energy parameters user will be prompted for password. If
correct password is entered, the user will be able to reset all energy
parameters. The password will be 1 grater than the main password.