Rayleigh Instruments RI-D384-C Operating Instructions Download Page 2

 

Sheilds Ensviromental Services RI-D384-C ( Page 2 of 4 )DM-V1.10-Rayleigh Instruments 13-04-16 

ONLINE PAGE DESCRIPTION 

There are 2 dedicated keys labelled as PAGE and PRG with symbols 

       and       to read meter parameters. 

 At power on the meter displays average phase to neutral voltage and 

active energy of three phases. If any key is not pressed for 60 

seconds the unit resumes manual mode. 

KEY 

PRESS 

PARAMETER 

KEY 

DESCRIPTION 

ONLINE PAGE DESCRIPTION FOR 3P4W and 3P3W 

Press 

page 

(   ) key 

(1st time) 

 

—— 

Displays line to neutral 

voltage of three phases 

Press (   ) key 

Displays line to line voltage 

of three phases (

)

 

Press 

page 

(   ) key 

(2nd time)  

—— 

Displays phase current of three phases 
(

Press 

page 

(   ) key 

(

3rd time

)   

 

—— 

Displays average phase to neutral 

voltage, current and power factor of 

three phases and frequency 

Press (   ) key 

  

Displays average line to line voltage, 

current and power factor of three phases 
and frequency (

Press 

page 

(   ) key 

(4th time)     

—— 

Displays power factor of three phases 

and frequency 

Press (   ) key 

1st time 

Displays active power of three phases 

Press (   ) key 

2nd time 

Displays reactive power of three phases 

Press (   ) key 

3rd time 

Displays apparent power of three  

phases 

Press (   ) key 

4th time 

Displays total active power of three 
phases (

Press (   ) key 

5th time 

Displays total reactive power of three 
phases (

Press (   ) key 

6th time 

Displays total apparent power of three 
phases (

Press (   ) key 

7th time 

Displays Max (2

nd

 row) and Min (3

rd

 row) 

demand of total active power (

Press (   ) key 

8th time 

Displays Max (2

nd

 row) and Min (3

rd

 row) 

demand of total reactive power (

Press (   ) key 

9th time 

Displays Max demand of total apparent 
power (

SERIAL NUMBER DESCRIPTION 

Press (   ) key for 10 seconds to 8 digit serial number only for 10 

seconds on the 2nd and 3rd lines of the display 

CONFIGURATION 

There  are  3  dedicated  keys  with  symbols  marked  as  
    ,    and       use these 3 keys to enter into configuration menu or 
to  change the settings.  

Note  : 

The  settings  should  be  done  by  a  professional,  after 

going  through  this  users  manual  and  after  having  understood  the  

application situation. 

For the configuration setting mode: 

● Use     and        keys for 3 seconds to enter or exit from the  

configuration menu. 

● Use     shift key to move curser left or right by one digit each time. 

After last digit of display cursor shifts to 1st digit of display. 

● Use     increment key for increasing the parameter value. 

● Use       key to save the setting and move on to the next page. 

● Use     and    keys to go back to the previous page. 

Config 

Page 

Function 

Range or 

Selection 

Factory 

Setting 

 

Password 

0000-9999 

1000 

1.0 

Change Password 

No/Yes 

No 

1.1 

New Password 

0000-9998 

1000 

2.0 

Network Selection 

3P4W 

3P3W 

1P2W-P1 

1P2W-P2 

1P2W-P3 

3P4W 

3.0 

CT Secondary 

1-5A 

5A 

4.0 

CT Primary  

5A - 10000A 

5A 

5.0 

PT Secondary  

100 - 500V 

350V 

6.0 

PT Primary 

100-500KV 

350V 

7.0 

Slave ID (Address) 

1-255 

8.0 

Baud Rate 

300, 600, 1200, 

4800, 9600 & 

19200 

9600 

9.0 

Parity 

None, Even, Odd 

None 

10.0 

Stop Bit 

1 or 2 

11.0 

Back Light 

0-7200S 

0000 

12.0 

Demand Interval Method 

Sliding/Fixed 

Sliding 

13.0 

Demand Interval Duration 

1-30 

15 

14.0 

Demand Interval Length 

1-30min 

15.0 

Max auto Pages 

1 to 18 

18 

16.0 

Change Page Sequence 

No/Yes 

No 

16.1 

Page Sequence 1 

No/Yes 

No 

16.2 

Page Sequence 2 

No/Yes 

No 

16.3 

Page Sequence 3 

No/Yes 

No 

16.4 

Page Sequence 4 

No/Yes 

No 

16.5 

Page Sequence 5 

No/Yes 

No 

16.6 

Page Sequence 6 

No/Yes 

No 

16.7 

Page Sequence 7 

No/Yes 

No 

16.8 

Page Sequence 8 

No/Yes 

No 

16.9 

Page Sequence 9 

No/Yes 

No 

16.10 

Page Sequence 10 

No/Yes 

No 

16.11 

Page Sequence 11 

No/Yes 

No 

16.12 

Page Sequence 12 

No/Yes 

No 

16.13 

Page Sequence 13 

No/Yes 

No 

16.14 

Page Sequence 14 

No/Yes 

No 

16.15 

Page Sequence 15 

No/Yes 

No 

16.16 

Page Sequence 16 

No/Yes 

No 

16.17 

Page Sequence 17 

No/Yes 

No 

16.18 

Page Sequence 18 

No/Yes 

No 

17 

Reset Factory Default 

No/Yes 

No 

18 

* Password 

0001-9999 

1001 

Press 

page 

(   ) key 

(1st time) 

 

——- 

Displays average voltage line to neutral 

(1

st

 row), import active energy (2

nd

 row) 

and export active energy (3

rd

 row) of 

three phases (

Press (   ) key 

Displays average voltage line to neutral 

(1

st

 row), import reactive energy (2

nd

 

row) and export reactive energy (3

rd

 row) 

of three phases (

Press (   ) key 

3 seconds 

Displays average voltage line to neutral 

(1

st

 row) and apparent energy (3

rd

 row) 

of three phases (

For this key function in 1st row for 3P3W voltage will be 

average line to line. 

Note: 

For 3Phase 3Wire network only 

(

) marked page will be displayed. 

KEY 

PRESS 

PARAMETER 

KEY 

DESCRIPTION 

ONLINE PAGE DESCRIPTION FOR 1P2W-P1/P2/P3 

Press 

page 

(   ) key 

(1st time) 

 

—— 

Displays line to neutral 

voltage of selected phase 

Press 

page 

(   ) key 

(2nd time)  

—— 

Displays phase current of selected  

phase 

Press 

page 

(   ) key 

(4th time)     

—— 

Displays power factor of selected 

phase and frequency 

Press (   ) key 

1st time 

Displays active power of selected 

phase 

Press (   ) key 

2nd time 

Displays reactive power of selected 

phase 

Press (   ) key 

3rd time 

Displays apparent power of selected  

phase 

Press (   ) key 

4th time 

Displays MAX (2

nd

 row) and MIN (3

rd

 

row) demand of total active power 

Press (   ) key 

5th time 

Displays MAX (2

nd

 row) and MIN (3

rd

 

row) demand of total reactive power 

Press (   ) key 

6th time 

Displays total MAX demand of total 

apparent power 

Press 

page 

(   ) key 

(5th time)     

—— 

Displays average voltage line to 

neutral (1

st

 row), import active energy 

(2

nd

 row) and export active energy 

(3

rd

 row) of selected phase 

Press (   ) key 

1st time 

Displays average voltage line to 

neutral (1

st

 row), import reactive 

energy (2

nd

 row) and export reactive 

energy (3

rd

 row) of selected phase 

Press (   ) key 

2nd time 

Displays average voltage line to 

neutral (1st row) and apparent 

energy (3rd row) of selected phase 

Note: 

For 1Phase 2Wire network, only selected phase parame-

ter will be displayed 

Config 

Page 

Function 

Range or 

Selection 

Factory 

Setting 

18.01 

Reset Active Energy 

No/Yes 

No 

18.02 

Reset Reactive Energy 

No/Yes 

No 

18.03 

Reset Apparent Energy 

No/Yes 

No 

18.04 

Reset Max Power 

No/Yes 

No 

* For resetting energy parameters user will be prompted for password. If 

correct password is entered, the user will be able to reset all energy 

parameters. The password will be 1 grater than the main password. 

Summary of Contents for RI-D384-C

Page 1: ...ty of the operating personnel as well as the instrument If the equipment is not used in the manner specified by the manufacturer it might impair the protection provided by the equipment CAUTION Read the instructions prior to installation and operation of the unit CAUTION Risk of electrical shock WIRING GUIDELINES WARNING 1 To prevent the risk of electric shock power supply to the equipment must be...

Page 2: ...ack Light 0 7200S 0000 12 0 Demand Interval Method Sliding Fixed Sliding 13 0 Demand Interval Duration 1 30 15 14 0 Demand Interval Length 1 30min 1 15 0 Max auto Pages 1 to 18 18 16 0 Change Page Sequence No Yes No 16 1 Page Sequence 1 No Yes No 16 2 Page Sequence 2 No Yes No 16 3 Page Sequence 3 No Yes No 16 4 Page Sequence 4 No Yes No 16 5 Page Sequence 5 No Yes No 16 6 Page Sequence 6 No Yes N...

Page 3: ... Integer 40028 0x1C Page Sequence 12 1 18 1 First page 18 Last page 1 Integer 0 1 Resolution 1 0 1 seconds 0 01 Resolution 1 0 01 KWh Address Hex Address Parameter Range Length Register Data Structure 40029 0x1D Page Sequence 13 1 18 1 First page 18 Last page 1 Integer 40030 0x1E Page Sequence 14 1 18 1 First page 18 Last page 1 Integer 40031 0x1F Page Sequence 15 1 18 1 First page 18 Last page 1 ...

Page 4: ...rvices RI D384 C Page 4 of 4 DM V1 10 Rayleigh Instruments 13 04 16 Specifications subject to change as development is a continuous process RAYLEIGH INSTRUMENTS LIMITED Cutlers Road South Woodham Ferrers Chelmsford CM3 5WA UK ...