SPECIFICATIONS
DISPLAY
Liquid crystal display with backlight
1 line, 4 digits and 2 line, 7 digits per line to show
electrical Parameters
LCD INDICATIONS
- Communication in progress
- Maximum Demand of Power
WIRING INPUT
3.Ø - 4 wire, 3.Ø - 3 wire, 2.Ø - 3 wire, 1.Ø - 2 wire
RATED INPUT VOLTAGE
11 to 300Vac (L-N); 19 to 519Vac (L-L)
FREQUENCY RANGE
45-65Hz
CT PRIMARY
1A to 10000A (Programmable for any value)
CT SECONDARY
Nominal 5A (min 11mA, Max 6A)
CT Burden
0.5VA @ 5a per phase
PT PRIMARY
100 to 500KVac (Programmable for any value)
PT SECONDARY
100 to 500Vac (Programmable for any value)
DISPLAY UPDATE TIME
1 Second for parameters
DISPLAY SCROLLING
Automatic / Manual
POWER CONSUMPTION
<8VA
TEMPERATURE
Operating
: -10 to 55°C
Storage
: -20 to 75°C
HUMIDITY
85% non-condensing
MOUNTING
Panel mounting
WEIGHT
208gms
OUTPUT
Pulsed Output : Voltage range External 24VDC max
Current capacity : 100mA
INSTALATION CATEGORY
Category III
SERIAL COMMUNICATION
Interface Standard
and protocol
RS485 & Modbus RTU
Communication address
1 to 255
Transmission Mode
Half duplex
Data types
Float and Integer
Transmission distance
500 Meter maximum
Transmission speed
300, 600, 1200, 2400, 4800
9600, 19200 (bps)
Parity
None, Odd, Even
Stop bits
1 or 2
Response time
100mS
ACCURACY
Measurement
Accuracy
Voltage V
L-N
±0.5% of Full Scale
Voltage V
L-L
±0.5% of Full Scale
Current
±0.5% of Full Scale
Frequency
For L-N Voltage >20V
For L-L Voltage >35V
±0.1% of Full Scale
Active Power
±1%
Reactive Power
±1%
Apparent Power
±1%
Power Factor
±0.1%
Active Energy
±1%
Reactive Energy
±1%
MAX / Min Active Power
±1%
MAX / MIN Reactive Power
±1%
MAX Apparent Power
± 1%
RESOLUTION
PT Ratio x CT Ratio
KWh / KVAh / KVArh
<15
0.01K
<150
0.1K
<1500
1K
<15000
0.01M
<150000
0.1M
NOTE:
1) For Voltage, Current, Power, resolution
is automatically adjusted.
2) For Power Factor resolution is 0.001
SAFETY PRECAUTIONS
All safety related codifications, symbols and instructions that
appear in this operation manual or on the equipment must be
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If the equipment is not used in the manner specified by the
manufacturer it might impair the protection provided by the
equipment.
CAUTION
Read the instructions prior to installation
and operation of the unit
.
CAUTION
Risk of electrical shock
WIRING GUIDELINES
WARNING
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while installing the wiring.
2. Wiring shall be done strictly according to the terminal layout.
Confirm that all connections are correct.
3. Use lugged terminals.
4. To reduce electromagnetic interference use of wires with
adequate ratings and twists of the same in equal size shall
be made with shortest connections.
5. Layout of connecting cables shall be away from any internal
EMI source.
6. Cable used for connection to power source, must have a
cross section of 0.5mm
2
to 2.5mm
2
. These wires shall have
current capacity of 6A.
7. Copper cable should be used (Stranded or single core
cable).
8. Before attempting work on the device ensure absence of
voltages using appropriate voltage detection device.
INSTALLATION GUIDELINES
CAUTION
1. This equipment, being of a built-in-type, normally becomes
a part of a main control panel and in case the terminals do
not remain accessible to the end user after installation and
internal wire.
2. Conductors must not come into contact with the internal
circuitry of the equipment or it may lead to a safety hazard
that may in turn endanger life or cause electrical shock to
the operator.
3. Protection & disconnection means must be installed
between power source and supply terminals to facilitate
power ‘ON’ or ‘OFF’ function & must be installed in a
convenient position normally accessible to the operator.
4. Before disconnecting the secondary of the external current
transformer from the equipment, make sure that the current
transformer is short circuited to avoid risk of electrical shock
and injury.
5. The equipment shall not be installed in environmental
conditions other than those mentioned in the manual.
6. The equipment does not have a built-in-type fuse.
Installation of external fuse of rating 275Vac / 0.5Amp for
electrical circuitry / battery is highly recommended.
DIMENSIONS (All dimensions in mm)
TERMINAL CONNECTIONS