Wuhan Raycus Fiber Laser Technologies Co., Ltd.
User Guide of RFL-C3000XZ~RFL-C12000XZ
24
After pressing the current panel emergency stop, 11, 14 open circuit, otherwise for short
circuit.
12
OUT
Front panel emergency stop output 2, relay contact output, passive contact,
electric current
100mA, voltage
<
30V
;
After pressing the current panel emergency stop, 12, 13 open circuit, otherwise for short
circuit.
13
OUT
15
OUT (FET S pole)
The main power supply has been switched on for output indication, MOSFET D and S
poles output;
electric current< 0.5A, voltage < 60V.
16
OUT (FET D pole)
17
IN
Interlock1 input, active contact, normal short connection 17, 20, no external voltage or
grounding.
20
IN
18
IN
Interlock2 input, active contact, normally short connection 18, 19, no external voltage or
grounding.
19
IN
21
IN
When the remote main power is powered on, it is same with the function of the Power
button on the front panel. When Pins 21 and 22 are closed, the main power supply is
started. The active outlet points can’t not be externally voltage or grounded.
22
IN
23
OUT
The laser has been energized and output;
OFF - the laser key switch is in the OFF position;
Closed - the laser key switch is in the ON or REM position;
Passive contact, external voltage signal, voltage less than 30V, electric current less than
1A.
24
OUT
a)
Mode Signal
Figure 13 Mod signal schematic diagram
This signal is 5/24V compatible, and reverse connection is not allowed.
When the key switch is turned to “ON” and the laser works in the external laser control mode, the
MOD is used to control the laser emission and turn off;
When the key switch is turned to “REM” and the laser is working in the external laser control mode,
MOD and XP1-A2 (at this time the A2 position light enable signal) are united to control the emission and
turn off of the laser (in REM mode, the laser can only be controlled by A2, need to be customized).
b)
Passive Laser-Emitting Indication and Main Power-On Indication