2  |  nVent.com

TraceTek tag

(TT-TAG)

Hold-down clip

(TT-HDC)

Modular end termination

(TT-MET-MC)

Modular sensing cable

Modular

sensing

cable

Modular branching connector

(TT-MBC-MC)

Modular leader cable

(TT-MLC-MC)

Modular jumper cable

(TT-MJC-xxx-MC)

Note:

•  Drawing not to scale.

•  Not shown: heat-shrinkable tube 

   to cover each connection.

Modular jumper cable

TraceTek alarm 

module (several 

models available;

TTDM alarm and

locating module 

is shown)

Factory-installed connector

Modular end termaination

TT-MET-MC

Modular sensing cable

(TT3000-xxx-MC or

TT5000-xxx-MC or

TT5001-xxx-MC)

Heat-shrinkable tube 

(for extras, order TT-COS)

supplied with cable

Factory-installed

end termination

Modular sensing cable

(TT3000-ZONE-MC or

TT5000-ZONE-MC or

TT5001-ZONE-MC)

Heat-shrnkable tube 

(for extras, order TT0COS)

supplied with cable

Factory-installed connector

General Layout of TraceTek System

Modular Sensing Cable   (with factory-installed connectors)

Zone Sensing Cable

 

(with factory-installed connector and end 

termination)

1.  Prepare the area where the sensing cable will be located.

•  Verify that major construction is complete.
•  Clean the area where the cable will be installed to remove 

debris and sources of contamination. For techniques in 

double-containment piping, consult the TraceTek  

Double-Containment Installation Guide (LIT-138).

•  For sumps, containment trenches, and subfloor applications, 

install TraceTek hold-down clips. For TraceTek TT3000 sensing 

cables, use 1/4” hold-down clips (TT-HDC-1⁄4...); for TraceTek 

TT5000 series sensing cables, use 1/2 inch hold-down clips 

(TT-HDC-1⁄2-NA-50).
Clean the floor surface where hold-down clips will be placed so 

adhesive can work properly.
Position hold-down clips so the sensing cable will provide the 

desired leak detection coverage. To best secure the cable, 

alternate the direction of the hold-down clips, and install them 

at intervals of no greater than 6 feet (2 m) and at every change 

in direction (at sides of trench, for example).

Important: Let the adhesive dry per manufacturer’s  

recommendation before proceeding with sensing-cable  

installation.

•  In sumps that may collect water, mount TT5000 series sensing 

cable vertically to allow it to detect hydrocarbons floating on water; 

prepare for this by installing hold-down clips up side of sump.

TT-HDC-1⁄4 or

TT-HDC-1/4-200-NA

TT-HDC-1⁄2-NA-50

< 6 ft (2 m)

Installation Steps