10 | nVent.com
D: STATUS - LEDS
Table 3: LED status of RAYCHEM NGC-40-SLIM module
Note: For the SLIM module, when ALL LEDs are flashing red, the unit has lost
factory calibration, cannot be communicated with, and must be returned to the
factory for repair/replacement.
2�2 Mounting and wiring NGC-40-SLIM module
Figure 2: Mounting RAYCHEM NGC-40-SLIM module onto DIN rail
State
LED
Status
Network
Current
TS 1
TS 2
TS 3
Trip
OFF
No Power
No current
No alarm
No alarm
No alarm
Not Tripped
RED
Device-reset
alarm is
active
Tripped
GRN
Normal
operation, no
internal faults
Flicker on
receipt of
CAN packet
Current
YEL
In Boot
Loader mode
Flicker on
transmission
of CAN
packet
Flash RED Internal Fault:
• Lost
calibration
TS 1sensor
failure alarm
TS 2 sensor
failure
alarm
TS 3 sensor
failure alarm
Flash GRN
Flash YEL
Tripper and
non-latching
Flash RED/
GRN
Factory
unlock /
un-calibrated
Flash RED/
YEL
Flash YEL/
GRN
Mounting the NGC-40-SLIM
2
1
2
1
Each NGC-40-SLIM mounts on a DIN35 rail.
MOUNTING
: Insert the rear bottom of the module into the DIN rail, then push up and
inwards to engage the clip.
Removal
: Push the module upwards to
disengage the clip, than rotate the module
toward you.