1. Description
1.1 Intended Purpose
The electronic control unit EMDR-10 is specifically designed for the control of gutter heating
systems. Depending on outdoor temperature and moisture in the gutter the heating cable will
only be switched on if necessary to ensure a correct drain of the snow water.
1.2 technical Data
control Unit
Supply voltage
230 VAC, ±10%, 50Hz
Power consumption
max. 4 VA
Max. Switching capacity
Imax 10(4)A / 230 VAC, SPST,potential 230 VAC
Temperature
–3°C to +6°C (factory s2°C)
adjustment range
Lower limit temperature test
–25°C to –5°C (factory setting adjustment range –15°C)
Operating differential
±0.5 K
Measuring accuracy
±1.5 K
Moisture adjustment range
1 (max. sensitivity) to 10 (min. sensitivity) (factory setting 5)
Post heating time
0 to 60 minutes (factory setting 60 minutes)
adjustment range
Alarm relay
Imax 2(1)A / 230 VAC, SPDT, potential-free
Moisture sensor (output)
Imax 1A / 230 VAC, SPST potential
230 VAC with fuse 5 x 20mm T1A
according to IEC127-2/V
Mounting
DIN rail according to DIN EN 50022-35
Low voltage directive
EN 60730
EMC
EN 50081-1 (emission) and
EN 50082-1 (immunity)
Terminals
2.5 mm
2
(stranded conductors), 4 mm
2
(solid conductors)
Protection class
II (panel mounted)
Housing
Ambient temperature range* 0°C to +50°C
Ingress protection
IP20
Housing material
Noryl (self-extinguishing according to UL 94 V-0)
Weight
approx. 350 g
Dimensions
106 x 90 x 58 mm
* Continuous operation must be assured and the device must be protected from the penetration
of moisture.
ambient temperature sensor
Sensor type
VIA-DU-10
Ingress protection
IP54
Terminals
2.5 mm
2
Sensor cable
2 x 1.5 mm
2
, max. 100 m (not included)
Exposure temperature
–30°C to +80°C
Mounting
Wall mounting
Moisture sensor (HaRD-45)
Sensor type
PTC
Power consumption
9 W to 18 W
Ambient temperature range
–30°C to +65°C continuous
Supply voltage
230 VAC, ±10%, 50Hz
Connection cable
3 x 1.5 mm
2
, 4 m, the connection
cable can be extended to max. 100 m at 3 x 1.5 mm
2
5