4.3.6 “COMMUNICATIONS SETUP...” Sub-Menu
The settings found in this sub-menu must be configured whenever an optional
communications board is installed in the Control Module. These parameters are common to
both control points, EXCEPT the “HTCBUS ADDR”, “MODBUS ADDR”, and “MODBUS SUBADDR”
parameters, which must be defined for each control point individually.
CONTROL SETPOINT
=
20°C
LO TS 1
=
-10°C
LO LOAD
=
1.0 A
HI GFI
=
50 mA
GFI TRIP
=
75 mA
TS ALARMS CONFIG...
OTHER ALARMS CONFIG...
POINT SETUP...
COMMON SETUP...
COMMUNICATIONS SETUP...
--- END ---
COMMUNICATIONS Sub-Menu
PROTOCOL
=
{HTCBUS or MODBUS ASCII
or MODBUS RTU}
HTCBUS ADDR
=
{1 to 1,6777,215}
(only if PROTOCOL= HTCBUS)
MODBUS ADDR
=
{1 to 247}
(only if PROTOCOL is not
HTCBUS)
MODBUS SUB
ADDR
=
{0 to 31}
(only if PROTOCOL is not
HTCBUS)
BAUD RATE
=
{AUTO or 9600 or 4800 or
2400 or 1200 or 600 or 300}
PARITY
=
{NONE or ODD or EVEN}
(only if PROTOCOL is not
HTCBUS)
HARDWARE
=
{NONE or MODEM or RS-232
or RS-485}
DRIVER
=
{AUTO or RS-485 or RS-232
or MODEM}
PROFILE
=
{AUTO or
FLOW CONTROL RS-232 or
STANDARD RS-232 or
3-WIRE RS-232 or
RS-485 or
EXTERNAL MODEM or
1200 BAUD MODEM or
300 BAUD MODEM}
Tx DELAY
=
{0.00 to 2.50} S
--- END ---
Table 4.10