Rev. 1.0 (12/19/2022)
13
6.
Ensure both the neutral and ground have been terminated in their correct locations
and torqued to manufacturer specifications.
7.
If there will be both a grid and generator input, land the grid input on the line side of
the disconnect.
The generator input will be terminated on the “GEN” breaker on the
Sol-Ark.
8.
The RaVolt enclosure arrives pre-wired and pre-configured to allow the load side of
this disconnect to flow through the inverter, into the load center and into the home.
After landing the grid and/or generator inputs, this disconnect is complete.
AC Output:
1.
Ensure there is no power to the load center using a voltmeter.
2.
Remove screws and remove the front plate from the load center.
3.
After cable has been pulled from the load center on the RaVolt enclosure to the AC
disconnect on the side of the home or dwelling, begin to make terminations in the
appropriate locations within the load center.
4.
Ensure cables have been labeled and terminated on the load side of the 200 A
breaker according to the manufacturer specifications, and per NEC code.
5.
Ensure both the neutral and ground have been terminated in the correct locations
within the load center.
6.
The RaVolt enclosure arrives pre-wired and pre-configured to connect the load
center to the inverter. After terminating this AC out cable, this load center is
complete.
PV Input:
1.
Ensure there is no power on the incoming PV cable.
DO NOT MAKE MC4 HOME RUN
CONNECTIONS BEFORE TERMINATING THIS DC DISCONNECT.
2.
Ensure cables have been correctly labeled to clearly indicate different strings,
positive and negative.
3.
Run PV cables from the array, into a drip loop, into the weather head. This will run
directly into the DC disconnect on the side of the enclosure.
4.
Place the switch in the “off” position and remove the screws from the DC disconnect
cover. Remove the cover.
5.
Begin to make terminations within the DC disconnect according to the manufacturer
specifications.
Refer to the one line document for detailed termination
instructions.
6.
After terminations are made and verified, replace screws and DC disconnect cover.