P/N RE - 102 / 104 Rev. No. 0
21
4.3.5.1.
Zone 1
From this menu, the zone 1 loop can configured as
enable, disable, Zone test and Walk test. The default
option is ‘Enable’. To change the options press ‘Enter’ key,
then change the options by using the left/ right cursor
keys. The Screen will be as shown below.
Enable Mode: In this mode the zone will be in normal
condition to detect the fire with detectors and manual
call point (normally open devices).
Disable Mode: In this mode the zone is disabled with loop
voltage cut off.
Note:
Avoid disabling any zone unless it is really
essential.
Zone Test Mode: In this mode the zone is Tested for Fire,
Open, Short and Isolate automatically without disturbing
the normal operations.
Walk test Mode: In this mode the selected zone is used to
check all the loop devices manually one by one. The
signal from the Initiating device will cause the panel in the
alarm mode. The panel automatically get silenced and
reset after a specific period without activating the fire
relay. In this mode reset is done for only that particular
zone. When entering into this mode the Fire relay output
disablement is activated automatically and it will go back
to previous status while we are coming out from this
mode. For other zones that are not in walk test mode, if
they sense any fire, then the panel will go to normal alarm
mode and walk test zone changed to alarm mode
automatically.
1. Zone 1
<Enabled>