43
8 Gas connection
8 Gas connection
CAUTION!
Danger to life!
Connecting incorrectly may result in burns.
Observe local regulations.
DANGER!
Poisoning hazard!
Make sure that factory settings conform with
actual connection conditions:
> Perform exhaust gas analysis when first
commissioning steam- and convection burn-
ers (CO, CO
2
)
> record these values.
If undiluted CO levels are above 150ppm for
convection and 400ppm for steam, a compa-
ny-trained and certified technician must be
called in to check burner settings in accordance
with setting instructions, and adjust these set-
tings if needed.
Observe all local gas company regulations!
Australian Supplement to Gas Installation
> To be installed only by authorised person in
accordance with AS 5601, local authority, gas,
electricity, any applicable statutory regulations
and manufacturer requirements.
> Particular attention should be given to rele-
vant requirements regarding ventilation.
> This appliance is not suitable for use in marine
environment.