48
8 Gas connection
8 Gas connection
CAUTION
Danger to life!
Connecting incorrectly may result in burns or
fire.
Observe local regulations.
DANGER
Poisoning hazard!
Make sure that factory settings conform with
actual connection conditions:
> Perform exhaust gas analysis when first
commissioning steam- and convection burn-
ers (CO, CO
2
)
> record these values.
If undiluted CO levels are above 150ppm for
convection and 400ppm for steam, a compa-
ny-trained and certified technician must be
called in to check burner settings in accordance
with setting instructions, and adjust these set-
tings if needed.
Observe all local gas authority regulations!
Check the type of gas available and the dynamic
connection pressure against the values specified
on the unit.
! mbar