- 21 -
V-09 05/2014
4
Flue gas connection /gas consumption
For gas unit exhaust unit must be placed under an
exhaust hood externally vented (observe your local
regulations). Extractor hood
pic. 4
• The appliance must be installed on noncombus-
tible floors only
Room ventilation
The rooms in which these appliances are installed
must be well ventilated, in order to prevent an unac-
ceptable build-up of harmful combustion products.
We recommend to service the gas units at least
Unit size
6x1/1 GN
6x2/1 GN
10x1/1 GN 10x2/1 GN
20x1/1 GN 20x2/1 GN
Room size free ventilation
68
146,5 115,1 235,5 230,2
470,9
Room size permanent ventilation
34
73,3
57,6
117,7
115,1
235,4
Combustion air supply
24,9 yd
3
/h
58,9 yd
3
/h
45,8 yd
3
/h 94,2 yd
3
/h
91,6 yd
3
/h
188 yd
3
/h
Waste gas volume
49,7 yd
3
/h
141,3 yd
3
/h
102 yd
3
/h
235,4 yd
3
/h
196,2 yd
3
/h
458 yd
3
/h
Waste gas temperature
662°F 968°F 878°F 1094°C 806°F 968°F
Gas consumption
Gas type Required Wobbe index
max. consumption on nominal heat load
flow-
(15°C, 1013mbar)
6x1/1GN 6x2/1GN 10x1/1GN 10x2/1GN 20x1/1GN 20x2/1GN
pressure Wi
Ws
gross calorific value (BTU/hr)
Nat. gas
in/wc MJ/m
3
MJ/m
3
49000 106000 83500 170000 167000 340000
Gas “A”
6,5 -10,0 45,67 50,72
49,44 ft
3
/h 107,35 ft
3
/h 82,98ft
3
/h 171,9 ft
3
/h 168,4 ft
3
/h 348,2 ft
3
/h
gross calorific value (lb/hr)
LPG
in/wc MJ/m
3
MJ/m
3
48200 103800 81500 166800 163000 333500
Gas “E”
10,0 -15,0 80,58 87,33
2,69 lb/h 5,86 lb/h
4,61 lb/h
9,5 lb/h
9,1 lb/h 18,8 lb/h
Exhaust gas- and room volume
(All values in cu/yd)
Free ventilation
= Combustion air supply through windows and doors
Permanent ventilation
= Combustion air supply by two openings to the outside with a free cross section of
23 inch
2
(one opening near the ceiling, the other opening near the floor)
DANGER
Gaseous combustion product (CO and CO2)
Suffocation hazard
The rooms in which these appliances are installed must be well ventilated, in order to prevent an unaccept-
able build-up of harmful combustion products.
once a year in accordance with the specified standards.
After maintenance or repair works the compensation hose of the gas valve has to be checked for tight fit.
After maintenance or repair works a leak test of all gas components has to be carried out.
Installation must conform to:
CGA-B 149.1 natural gas code, CGA-B 149.2 propane gas code
Gas connection:
Adapter inch thread to NPT is included in the starter kit (can be found in the cooking cabinet)