background image

Page 6

Programming Options for SmartRescue

Step 7

Mount the front cover back onto the enclosure.

Step 8

Programming Options for SmartRecue

Option 1

Factory Default:

The Emergency Phones will call directly offsite and not stop at the SmartRescue. That phone’s button will 

light at the SmartRescue during the call.

(Keep in Default Mode if site is not manned 24/7 to answer calls onsite)

Option 2

Program the SmartRescue to Allow the Emergency Phones to call the SmartRescue first, then outside 

number(s): 

(Used when staff are available at certain times to answer calls)

 

1. Hold down Red Disconnect and Submaster 1 buttons for 5 seconds

 

2. Release buttons (you will hear a confirmation tone)

 

3. Press Phone 2 button, then Red button, and then the Phone 1 button

 

4. Press Submaster 2 button, then Submaster 1 button (you will hear a confirmation tone)

*Note: 

If you need to reprogram the SmartRescue back to Default Mode see page 13.

Programming the SmartRescue

Summary of Contents for SmartRescue 5

Page 1: ...Corporate Circle Sussex WI 53089 800 451 1460 262 246 4828 fax www rathmicrotech com www area of refuge com RP8500510 Ver 1 12 17 Made in the USA 3 Year Warranty SmartRescue 5 10 Installation Operati...

Page 2: ...lation Requirements Page 3 Installation Steps 1 4 Page 3 Wiring SmartRescue to 120V Power Source Page 4 Wiring Emergency Phones to SmartRescue Page 5 Programming Options for SmartRescue Page 6 Powerin...

Page 3: ...rgency Phone to the SmartRescue Base Station Use 24V 18 2 wire if remote powering the Emergency Phones Pre Installation Requirements Step 1 Remove the front cover from the SmartRescue and mount the Sm...

Page 4: ...Step 5 Wire the SmartRescue to a 120V power source Note Models 2500 205 and 2500 210 come with a Plug in Transformer Wiring the SmartRescue V V L N GROUND NEUTRAL 120vac HOT Yellow PIN 1 Green PIN 2...

Page 5: ...wires for each phone as shown on the SmartRescue Diagram To Phone Wire out to a standard 2 pair RJ11 phone jack Connect this jack to the 5 cord supplied by Rath Emergency Phone SmartRescue The Emergen...

Page 6: ...calls onsite Option 2 Program the SmartRescue to Allow the Emergency Phones to call the SmartRescue first then outside number s Used when staff are available at certain times to answer calls 1 Hold do...

Page 7: ...r 1 Submaster 2 Battery Green Full Charge Yellow Mid level Charge Red Low Charge Read all operating steps before proceeding Operation 1 Solid lit LED Phone Sub Master or Rescue Services indicates Call...

Page 8: ...entered in b Stop d To exit programm mode Press and hold Stop for 2 3 seconds until warble sound 2 Program the location message Note This is always done unless your Call Center requrest it not to be...

Page 9: ...e SmartRescue at any time to end the call 4 Emergency Phone places a call into the SmartRescue Base Station then an outside number or just to an outside number a You will hear an alternating audible t...

Page 10: ...9 1 6 all primary and secondary power supplies shall be monitores for the presence of voltage at the point of connection to the system 10 6 9 1 1 Failure of either the primary or secondary power supp...

Page 11: ...a simple fully functional solution to meet the 2010 and 2013 codes The Rath Alarm System checks the complete phone line system from the elevators to the machine room and from the machine room to the...

Page 12: ...y Phones MUST be in Consolidator Mode see page 12 Operation Lift handset To speak to individual phones connected to SmartRescue Press 1 Phone 1 Press 2 Phone 2 Press 3 Phone 3 Press 4 Phone 4 Press 5...

Page 13: ...ency Phone s to Consolidator Mode Only Elevator Industry Note Consolidator mode allows you to have up to 10 SmartPhones on a single telephone line and toggle between them from an outside call Programm...

Page 14: ...ions Submaster and Phone LEDs blinking on SmartRescue base Verify power is applied and the backup battery is connected properly to the SmartRescue board SmartRescue LEDs stay on Wires may be crossed V...