VENT-FREE APPLICATIONS (Additional Requirements)

COMBUSTION AIR CALCULATIONS WORKSHEET

1 .

Room

Width

Length

Height

x

 H=Vol. (ft3)

1 a .

1 b .

1 c .

1 d .

2 .

Total Volume (ft3 )sum of Volume (ft3) of all rooms                         (sum lines 1a. thru 1d.) 2 .

3 .

Max Supportable Btu/Hr=Total Volume (ft3) ÷ 50 x 1000                (line 2 ÷ 50 x1000)

3 .

4 .

4 a .  

3

                   Btu/hr 4 b .

3

                   Btu/hr 4 c .      

3

               Btu/hr 4 d .   

3

                 Btu/hr

Actual Btu/hr used = Sum Btu/hr of all fuel burning appliances inside the space
identified as rooms 1a. thru 1.b                                                                               (sum line 4a thru 4d.) 4 .

5 .

(Maximum Supportable Btu/Hr) minus (Actual Btu/hr Used)    (Line 3 - line 4)

5.                          *

*

If Line  is greater than zero, the Actual Btu/Hr Used is less than the Maximum Supportable Btu/Hr
and the space is considered UNCONFINED. No additional fresh combustion and ventilation is required.

*

If Line  is zero or less, the Actual Btu/Hr Used is greater than  Maximum Supportable Btu/Hr and
the space is CONFINED. You must either increase the Maximum Supportable Btu/Hr, decrease
the Actual Btu/Hr Used or operate as a Vented Appliance (see page 3).

WARNING: If the area in which the heater may be operated is smaller than that defined
as an unconfined space or if the building is of unusually tight construction, provide
adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or applicable local codes.

Unusually tight construction is construction where:
a) Walls and ceilings exposed to the outside atmosphere have a continuous water
vapor retarder with a rating of 1 perm or less with openings gasketed or sealed, and
b) Weather stripping has been added on openable windows and doors, and
c) Caulking or sealants are applied to areas such as joints around window and door
frames, between sole plates and floors, between wall panels, at penetrations for
plumbing, electrical, and gas lines, and at other openings.

WARNING: CARBON MONOXIDE POISONING MAY LEAD TO DEATH

When used without fresh air, gas log sets may give off carbon monoxide, an odorless, colorless,

poisonous gas. Some people, pregnant women, persons with heart or lung disease, anemia, or under

the influence of alcohol and persons at high altitudes are more affected by carbon monoxide than
others. Early signs of carbon monoxide poisoning resemble the flu: Headache, dizziness, and/or

nausea. If you have these signs, the gas log may not be installed or working properly, or the chimney

flue may be blocked.  GET FRESH AIR AT ONCE! Have gas log set and chimney flue serviced

before using again.

OPEN A WINDOW AN INCH OR TWO FOR ADEQUATE COMBUSTION AND

VENTILATION AIR WHEN USING YOUR VENT FREE GAS LOG ROOM HEATER

Minimum Clearances To Combustibles (VENT-FREE):

42"

15 1/2"

Figure 1

Side wall:

15 1/2" from side of fireplace opening. Figure 1

Ceiling:

42" from top of fireplace opening. Figure 1

Mantel: See Charts and Diagrams shown at Figures 2 and 3

N O T E :  "Clearances to Combustible Construction" are those distances
required to ensure that a fireplace mantel or facing will not catch fire. In most
cases they should also be adequate to prevent any discoloration or warping
due to heat. However, each and every Gas Log Installation (CHILLBUSTER
included) presents a different and completely unique set of circumstances
involving many variables beyond the control of the Gas Log Manufacturer.
These include paint or finish composition, previous exposure to heat,
methods and quality of construction, air flow patterns, glass doors, fans or
blowers, etc.. Because of these variables, we cannot guarantee that heat
warping or discoloration will never occur. The potential for heat warping or
discoloration may exist whether you are burning a CHILLBUSTER, some
other manufacturer's Gas Log or even wood.

5

Summary of Contents for CHILLBUSTER 5

Page 1: ...in a listed ventless firebox enclosure DO NOT install this appliance in a factory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs...

Page 2: ...s instructions stating it has not been tested or should not be used with unvented gas logs WARNING Any change to this heater or its controls can be dangerous Installation and repair should be done by...

Page 3: ...peration 3 Any outside air ducts and or ash dumps in the fireplace shall be permanently closed at time of installation WARNING Do not use a blower insert heat exchanger insert or other accessory not a...

Page 4: ...Btu Hr against Actual Btu hr Used Maximum Supportable Btu Hr 60 160 Btu Hr Actual Btu Hr Used 72 000 Btu Hr Excess Btu Hr 11 840 Btu Hr If Actual Btu Hr Used is greater than Max Supportable Btu Hr the...

Page 5: ...floors between wall panels at penetrations for plumbing electrical and gas lines and at other openings WARNING CARBON MONOXIDE POISONING MAY LEAD TO DEATH When used without fresh air gas log sets may...

Page 6: ...CLEARANCES YOU MUST OPERATE HEATER WITH CHIMNEY FLUE DAMPER OPEN Operate as a VENTED Heater See Page 3 ALL APPLICATIONS VENTED and VENT FREE OPERATION Installing Chillbuster 5 Burner Unit Into Firepl...

Page 7: ...oser the pieces the better the glowing ember effect WARNING Excessive amounts of Ember Material or Ember Material which is too tightly packed or exposed ports on Front or Middle burner can result in d...

Page 8: ...ers Rear Burner All positions are controlled through the Valve Knob CAUTION Cycling rapidly between burner settings can result in VENTURI LIGHT OFF This is characterized by a loud air flow noise resul...

Page 9: ...From THERMOPILE Valve Terminals 3 Way Control Selector Switch To ACCESSORY CONTROL Outside Terminal Piggy Back Outside Terminal instructions for individual Remote Accessory Options are included with t...

Page 10: ...resistant log in which the CRACKLER Sound Generator option for both the F10 AB and IRRC wireless remotes may be located NORMAL OPERATING CHARACTERISTICS Each and every CHILLBUSTER that leaves the fact...

Page 11: ...our log set When ordering parts always specify From information available on name plate attached to grate the following 1 Model number of the log set 2 Serial number of the log set 3 Type of gas natur...

Page 12: ...as set forth herein and applies only for the periods designated above 2 RASMUSSEN shall not be liable for any loss damage incidental or consequential damages of any kind whether based upon warranty c...

Page 13: ...CHANGES 2 03 page 1 standard update z21 11 2a 2001 DUE 4 03 standard update z21 11 2b 2002 DUE 12 03 Title change Customer Responsibilities And Annual Maintenance page 10 13...

Reviews: