Appendix F: PX3 Models with Residual Current Monitoring
705
power-sharing mode ends. For information on power sharing, see
Power-Sharing Restrictions and Connection (for iX7
™
Only) (on page 47).
RCM State Sensor
The RCM state sensor reports events based on residual current
thresholds or RCM self-test failure.
RCM state
Description
Normal Residual
current
is within normal range.
Warning Residual
current
is above warning level.
Critical
Residual current is above critical level. In addition to an event,
the CRITICAL state causes the PX3 front panel to display a
special error message.
Self-test active
RCM diagnostics are running.
Failure
RCM current sensor has malfunctioned. Contact Raritan
Technical Support.
Note: The factory default is to disable the Warning state. To define and
enable this state, see
Setting RCM Current Thresholds
(on page 710).
Important: When your PX3 enters the power-sharing mode, the RCM
sensor enters the 'unavailable' state and will not work before the
power-sharing mode ends. For information on power sharing, see
Power-Sharing Restrictions and Connection (for iX7
™
Only) (on page 47).
Summary of Contents for PX3-3000 series
Page 5: ......
Page 18: ...Contents xviii Index 841...
Page 93: ...Chapter 4 Connecting External Equipment Optional 69...
Page 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Page 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Page 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Page 823: ...Appendix K Additional PX3 Information 799...