Chapter 3: Initial Installation and Configuration
47
One device is connected to another device via two cascading cables -
USB and Ethernet cables.
Power-Sharing Restrictions and Connection (for iX7™ Only)
Two iX7
™
devices can share power supply to their controllers via
EXPANSION ports, so that when either iX7
™
controller fails to receive DC
12V power from its inlet(s), it continues to receive backup power from
another iX7
™
device which functions properly and therefore remains to be
accessible to users.
For documentation purpose, the term "power-sharing mode" is used
to describe the status when the 12V power supply from the inlet to
an iX7
™
controller fails, causing that controller to receive power from
another iX7
™
device.
Before making a power-sharing connection, first read
Power-Sharing
Configurations and Restrictions
(on page 49), and remove unsupported
equipment from BOTH iX7
™
PDUs.
After a PDU enters the power-sharing mode, some of its data/operations
remain to be available while other data/operations are no longer
available.
Unavailable data or operations on the PDU that enters the
power-sharing mode:
All outlets lose power, and enter the "disabled" state.
No outlet switching can be performed if the iX7
™
is an
outlet-switching capable PDU.
Summary of Contents for PX3-3000 series
Page 5: ......
Page 18: ...Contents xviii Index 841...
Page 93: ...Chapter 4 Connecting External Equipment Optional 69...
Page 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Page 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Page 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Page 823: ...Appendix K Additional PX3 Information 799...