
Chapter 8: Using the Command Line Interface
522
Example 3 - Combination of SSID and PSK Parameters
This multi-command syntax configures both SSID and PSK parameters
simultaneously for the wireless feature.
config:#
network wireless SSID myssid PSK encryp_key
Results:
The SSID value is set to myssid.
The PSK value is set to encryp_key.
Example 4 - Combination of Upper Critical, Upper Warning and Lower
Warning Settings
The following multi-command syntax configures Upper Critical, Upper
Warning and Lower Warning thresholds for the outlet 5 RMS current
simultaneously.
config:#
sensor outlet 5 current upperCritical disable upperWarning enable
lowerWarning 1.0
Results:
The Upper Critical threshold of outlet 5 RMS current is disabled.
The Upper Warning threshold of outlet 5 RMS current is enabled.
The Lower Warning threshold of outlet 5 RMS current is set to 1.0A
and enabled at the same time.
Load Shedding Configuration Commands
This section applies to outlet-switching capable models only.
A load shedding configuration command begins with
loadshedding.
Unlike other CLI configuration commands, the load shedding
configuration command is performed in the
administrator mode rather
than the configuration mode. See
Different CLI Modes and Prompts
(on
page 368).
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...