Chapter 8: Using the Command Line Interface
384
Outlet Pole Sensor Threshold Information
This command is available for an in-line monitor only, including
PX2-3000 and PX3-3000 series.
This command syntax shows the specified outlet pole sensor's
threshold-related information.
#
show sensor outletpole <n> <p> <sensor type>
To show detailed information, add the parameter "details" to the end of
the command.
#
show sensor outletpole <n> <p> <sensor type>
details
Variables:
<n> is the number of the outlet whose pole sensors you want to
query.
<p> is the label of the outlet pole whose sensors you want to query.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor Power
factor
sensor
activeEnergy
Active energy sensor