![Raritan EMX2-111 User Manual Download Page 434](http://html1.mh-extra.com/html/raritan/emx2-111/emx2-111_user-manual_3743227434.webp)
422
You can perform a Secure Copy (SCP) command to update the EMX
firmware, do bulk configuration, or back up and restore the
configuration.
In This Chapter
Firmware Update via SCP ....................................................................... 421
Bulk Configuration via SCP ..................................................................... 422
Backup and Restore via SCP................................................................... 423
Downloading Diagnostic Data via SCP .................................................... 424
Firmware Update via SCP
Same as any EMX firmware update, all user management operations are
suspended and all login attempts fail during the SCP firmware update.
For details, see
Updating the EMX Firmware
(on page 269).
Warning: Do NOT perform the firmware upgrade over a wireless
network connection.
To update the firmware via SCP:
1.
Type the following SCP command and press Enter.
scp <firmware file> <user name>@<device ip>:/fwupdate
<firmware file> is the EMX firmware's filename. If the firmware
file is not in the current directory, you must include the path in
the filename.
<user name> is the "admin" or any user profile with the
Firmware Update permission.
<device ip> is the IP address of the EMX that you want to update.
2.
When the system prompts you to enter the password for the
specified user profile, type it and press Enter.
3.
The system transmits the specified firmware file to the EMX, and
shows the transmission speed and percentage.
4.
When the transmission is complete, it shows the following message,
indicating that the EMX starts to update its firmware now. Wait until
the upgrade completes.
Starting firmware update. The connection will be closed
now.
Chapter 9
Using SCP Commands
Summary of Contents for EMX2-111
Page 69: ...Chapter 4 Connecting External Equipment Optional 57...
Page 78: ...Chapter 5 Using the EMX 66 EMX2 888...
Page 442: ...Appendix A Specifications 430 RS 485 Pin signal definition 6 D bi direction al Data 7 8...
Page 488: ...Appendix E LDAP Configuration Illustration 476 2 The EMX_Admin role is created...
Page 507: ...Appendix G RADIUS Configuration Illustration 495 Note If your EMX uses PAP then select PAP...
Page 512: ...Appendix G RADIUS Configuration Illustration 500 14 The new attribute is added Click OK...
Page 513: ...Appendix G RADIUS Configuration Illustration 501 15 Click Next to continue...