3

Then press CAL,we can calibrate the flow 
meter now. On the left bottom, the flow meter 
shows PErC and 100 above it. When the arrow 
is above, press CAL, the number will increase. 
When the arrow is downward, press CAL, the 
number decrease. Press RESET to change the 
direction of arrow. (The bigger of the number, 
the outlet of fuel less. Vice versa.) .

4

For example, the old factor is 100, means the 
outlet of fuel is 100l. If you want to reduce 2l, 
change the factor to 100.20. Then the outlet is 
98l.

5

For example, the old factor is 100, means the 
outlet of fuel is 100l. If you want to increase 2l, 
change the factor to 99.8. Then the outlet is 
102l.

6

Press and hold CAL, the calibration finish.

Cal

Cal

Cal

Q

TS

P

TS

L

G

AL

G

AL

L

Cal

+

-

FLOWRATE

8. Maintanence and trouble shooting

If the nozzle does not operate properly please check the feeding line and the pout for damages or 
contamination. Clean (wash off or rinse) the nozzle ore repair. 
For other dysfunction kindly contact manufacturer. 

This flow meter needs the battery with life span of at least 9000 hours (1 year) as the power supply. 
The short battery life will lead to the battery leakage during working and result in the damage of the 
flow meter. The standby life of this flow meter is designed as 2 years. Battery replacement every 
one year is recommended. In case the LCD display becomes dim or the Lbat occurs, it is time to 
replace the battery. We recommend the users to check the Battery electrode to clear the rusting in 
case. Take out the battery if the flow meter is not used for a long time.

6

+49 (6158) 92980-0

Summary of Contents for ZPA AB/Z

Page 1: ...0 i Weiterentwicklung im Sinne des Fortschrittes behalten wir uns vor Technical Modifications are subject to change Details techniques subject modification sans avis pr alable O P T I M I Z E S W O R...

Page 2: ...moved Always wear safety cloths respecting the applicable regulations for accident prevention Only use this device conforming to its purpose and function Improper use can cause severe injuries Caution...

Page 3: ...ery contents two nozzles DN 19 Dn15 with tubes 5 Assembling Installation Medium Diesel Adblue Kerosene Gasoline Inlet outlet 3 4 DN 19 DN 15 Accuracy 0 5 Repeatebility 0 3 Max pressure 20bar Voltage 3...

Page 4: ...ew 4 22 O Ring 26 5x2 5 1 6 Guard 1 23 O Ring 24x1 8 1 7 Screw 2 24 Nozzle body 3 housing 1 8 Lever 1 25 O Ring 30x1 5 1 9 Oil seal 1 26 Screw 4 10 Pin dia 1 5x15 2 27 Nozzle body 3 1 11 Pin dia 4x8 5...

Page 5: ...ress RESET until LCD displays full screen wait a few seconds stop press RESET The ow meter is ready to clear reset partial total 7 4 Example of Factor Calibration When the flow meter is stable or curr...

Page 6: ...Cal Cal QTS PTS L GAL GAL L Cal FLOWRATE 8 Maintanence and trouble shooting If the nozzle does not operate properly please check the feeding line and the pout for damages or contamination Clean wash...

Page 7: ...N TO PROTECT THE ENVIRONMENT The pertinent regulations for the registration setting up and operation of equipment for dealing with materials hazardous to water must always be complied with by the user...

Page 8: ...Fax 49 6158 92980 50 info rapid group de Rapid Group GmbH Bahnhofstra e 53 55 64560 Riedstadt Telefon 49 6158 92980 0 www rapid group de 8 49 6158 92980 0...

Reviews: