SECTION 12: VENTING - UNITARY HEATER
All general venting req
u
irements apply.
.
Exha
u
st end of fan
w
ill accept a 4'' (10 cm) vent pipe.
To prevent leakage of condensation, seal all the vent
joints
u
sing a high temperat
u
re silicone sealant.
The heater may be individ
u
ally vented or common
vented. When venting horizontally, a maxim
u
m of t
w
o
heaters can be commonly vented.
. When venting vertically, a maxim
u
m of
fo
u
r heaters can be commonly vented.
.
The CTHN
u
nitary heater may also be installed
u
nvented in certain circ
u
mstances according to
b
u
ilding ventilation codes. Refer to the codes on
for
f
u
rther information. Unvented operation also req
u
ires
compliance
w
ith the clearances to comb
u
stibles
given
.
12.1 Unvented Operation
S
u
fficient ventilation m
u
st be provided in the amo
u
nt
of 4 cfm per 1000 Bt
u
/h firing rate (United States); 3
cfm per 1000 Bt
u
/h firing rate (Canada).
Use of optional o
u
tside comb
u
stion air is not
recommended
w
ith
u
nvented heaters.
If exha
u
st fans are
u
sed to s
u
pply ventilation air, an
interlock s
w
itch m
u
st be
u
sed to prevent the heater
from coming on
w
hen the fans are off. This may be
done
u
sing a press
u
re s
w
itch.
12.2 Unvented Operation Termination
For
u
nvented operation, t
u
rndo
w
n type vent terminal
w
ith a screen m
u
st be installed at the exha
u
st end of
the fan. Vent terminal design shall not incorporate
backdraft flap.
FIGURE 27: Fan Termination
12.3 Horizontal Venting
In noncomb
u
stible
w
alls only, vent terminal
(P/N 02537801-1P) may be
u
sed.
For 4'' (10 cm) vents in either comb
u
stible or
noncomb
u
stible
w
alls,
u
se Tjernl
u
nd VH1-4 (P/N
90502100) or eq
u
ivalent, ins
u
lated vent terminal.
Follo
w
the man
u
fact
u
rer's instr
u
ctions for proper
installation.
For 6'' (15 cm) common vents in either comb
u
stible
or noncomb
u
stible
w
alls,
u
se Tjernl
u
nd VH1-6 (P/N
90502101) or eq
u
ivalent, ins
u
lated vent terminal.
Follo
w
the man
u
fact
u
rer's instr
u
ctions for proper
installation.
12.4 Vertical Venting
For 4'' (10 cm), an approved vent cap
(P/N 90502300) m
u
st be
u
sed.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502302) m
u
st be
u
sed.
For common vertical venting of more than t
w
o
12.5 Length Re
q
uirements
The maxim
u
m vent length allo
w
ed is 45' (13.7 m).
The maxim
u
m o
u
tside air s
u
pply d
u
ct length allo
w
ed
is 45' (13.7 m).
The total vent length, pl
u
s o
u
tside air d
u
ct length and
any extensions to minim
u
m heat exchanger lengths,
cannot exceed 65' (19.8 m).
Vent length sho
u
ld be limited to less than 20' (6 m).
If
u
sing extended heater lengths or vent lengths
greater than 20' (6 m), condensation
w
ill form in the
vent pipe. Ins
u
lation and additional sealing meas
u
res
(high temperat
u
re silicone at all seams) are req
u
ired.
Optional heat exchanger beyond minim
u
m lengths is
considered as vent length for length determination.
S
u
btract 15' (4.6 m) of maxim
u
m allo
w
ed vent or d
u
ct
length per vent elbo
w
if more than t
w
o are
u
sed.