background image

13 

 

 

 Temperature checking on the defrost probe 

>

 

press the “SET” switch for longer than 3 sec. (in case there is the alarm is 

activated it is necessary to switch the sound alarm off first). On the display there 

will appear “PS” symbol (password); 

>

 

 go to the “d/” parameter be means of the “UP” and/or “DOWN” switches, then 

press the “SET” switch - there will appear temperature of defrost probe and the  

symbol      or  

>

 

hold the “SET” switch  for longer than 3 sec. (after 60 sec. automatic return) – 

return to the temperature probe indication. 

Access for operator to parameters configuration and its modification 

 

>

 

press the „SET” switch for longer than 3 sec. (in case there is alarm activated, 

switch the sound alarm first). On the display will appear the „PS” symbol (service 

parameter password protected); 

>

 

go to the next parameters by means of the “UP” and/or “DOWN” switches; 

>

 

press the “SET” switch to view the current value of parameter setting; 

>

 

increase or decrease setting value by means of the “UP” and “DOWN” switches; 

>

 

press the “SET” switch to temporarily save the entered new value – it will cause 

as well return to the parameters list;  

>

 

repeat the above operations – if it is necessary; 

>

 

press and hold the “SET” switch for longer than 3 sec. – it will cause parameters 

saving and exit from the programming procedure. 

 

Warning:

 

If no button is pressed for 60 sec., all the changes made to the parameters, 

temporarily saved in the RAM, will be cancelled and the previous settings 

restored. 

If power is disconnected from the instrument before saving the settings (pressing 

the “SET” switch for 3 sec.), all the changes made to the parameters and 

temporarily saved will be lost.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Symbol

 

Parameter

 

Unit

 

Fabric 

setting

 

min.

 

max.

 

d8 

Alarm bypass time after defrost 

15 

A0 

Alarm and fan temperature differential  °C 

20 

AL 

Absolute or relative temperature for 

low temperature alarm 

°C 

150 

AH 

Absolute or relative temperature for 

high temperature alarm 

°C 

150 

Ad 

Temperature alarm delay 

min 

60 

199 

High temperature alarm activation = s AH 

High temperature alarm deactivation = s AH – A0   

Low temperature alarm activation = setting – AL 

Low temperature alarm deactivation = setting – AL + A0 

 

Summary of Contents for E

Page 1: ...1 TRANSLATED FROM MANUAL ORIGINAL USER REFRIGERATED COUNTERS AND MODULES Line E F 08 2021 EN ...

Page 2: ...Product characteristics 5 3 Cooling system diagram 5 4 Wiring system 6 5 Wiring system diagram 6 6 Drawings 7 7 Positioning start up and operation 9 8 Maintenance 10 9 Transport and equipment 10 10 Temperature controller manual 11 11 Interferences 15 12 Notes 15 ...

Page 3: ...c shock 2 In the event of sparks or breakdowns immediately disconnect the device from the power supply by pulling the plug from the socket and calling an authorized service technician 3 It is necessary to protect the wiring system and control system against water and mechanical damage 4 When servicing and replacing parts the device must be disconnected from the power supply 5 The power cord is dir...

Page 4: ...Max device model 2N housing made of stainless steel 202 107 device dimensions see table p 2 Important information on the rating label of each device In the case of contact with the service department prepare the following data for efficient service device type serial no of device Climatic class means the maximum ambient temperature at which the device works without disturbances Climatic class 3 ma...

Page 5: ...5 114 5 91 80 119 173 17 4 8 123 107 159 114 110 65 5 103 5 99 5 91 80 104 150 17 4 8 80 107 173 71 67 65 5 61 57 91 80 64 86 11 4 8 E Max E1 Max F Max 202 107 183 194 190 65 5 77 73 1 100 96 2 91 80 1 69 60 2 180 110 1 287 2 26 4 8 F NW 107 169 5 149 145 4 50 164 160 4 69 60 4 72 104 11 4 8 F NZ 107 93 5 3 193 189 4 53 5 119 17 4 8 3 COOLING SYSTEM DIAGRAM capillary chemical filter condenser comp...

Page 6: ...ance with the applicable regulations 6 Before carrying out any maintenance or cleaning turn off the device with the switch and then remove the plug from the mains socket 7 The device is started after connecting the plug to the mains socket and then by turning on the switch The backlight of the switch indicates that the device has been turned on 8 Any repair of electrical installation and replaceme...

Page 7: ...1 Max i L F Max counters Fig 3 Do not block the air outlet with products Place the goods on the platform Defrost water collection drain Aggregate cover Aggregate switch Lighting and backlight switch products depth with open door depth length products Electronic temperature controller Enlarged storage Standard storage ...

Page 8: ...x L E1 L E1 Max stand in front of the glass pane and slightly open it ca 10 than hold it with both hands and lift carefully up Warning In L E L E Max refrigerated counters it not allowed to leave glass pane in extremely open position this may damage the hinge Fig 7 L F L F Max L F NW L F NZ in order to wash the front glass pane it should be gently opened using handle Side glass pane Do not block t...

Page 9: ...e switches shown on Figure 1 The temperature inside the device is adjusted by means of the electronic temperature controller according to the instructions included in the chapter No 10 After switching the device on leave it empty until its switching off for the first time After that it is ready to be filled with products leaving free space as on the Figures 3 and 4 The maximum glass shelf load is ...

Page 10: ...t in aggregate overheating which consequently may lead to failure While cleaning the condenser be careful not to deform the fins Do not wash the device with a water jet It is not advisable to clean the condenser with a brush as it causes impurities penetration deep into the condenser fins and finally block the air flow completely For units with an automatic condensate evaporation system clean the ...

Page 11: ...ing off or when there is other procedure in progress 3 DEFROST The symbol is visible when there is defrost function switched on It flashes when the defrost start up is delayed by means of external switching off or when there is other procedure in progress 4 AUX The symbol is visible when there is additional AUX output activated 5 CLOCK The symbol is visible when there is clock switched on switchin...

Page 12: ...setting mode its pressing changes the information shown on the display parameter name parameter value pressed for longer than 3 sec will cause saving of the set parameters During setting parameter values pressed it will cause saving of the entered parameter value 9 DOWN DEFROST During normal operation of the controller pressed for longer than 3 sec will cause switching on off of the manual defrost...

Page 13: ...switches press the SET switch to temporarily save the entered new value it will cause as well return to the parameters list repeat the above operations if it is necessary press and hold the SET switch for longer than 3 sec it will cause parameters saving and exit from the programming procedure Warning If no button is pressed for 60 sec all the changes made to the parameters temporarily saved in th...

Page 14: ...t ended after exceeding the maximum duration rather than when reaching the end defrost set point The message disappears when the next defrost ends correctly EF displayed during operation or on power up operating parameter reading error controller automatic reset Alarm reappearance after automatic reset it is necessary to check the controller as there is no guarantee to keep the original precision ...

Page 15: ...um cleaner equipped with brush gently along fins to not to bend the lamella Device loaded with warm products hot air coming out of the aggregate chamber loud operation of the aggregate characteristic clicking coming out of the aggregate chamber every few minutes Goods loaded in the device chamber should be initially cooled up to maximum 4 C above the storage temperature Too high ambient temperatur...

Page 16: ... Reg No BDO 000009031 tel 48 81 742 53 10 do 14 e mail rapa rapa lublin pl Service e mail service rapa pl www rapa pl The package should be removed according to the regulations of environmental protection The warranty card and conditions are effective only in the area of Poland ...

Reviews: