PM3000 Power Quality Analyzer Factory Configurations
1ø Full PQ Flkr 7day
6
General Setup Values
Storage Mode: Adaptive Store
Recording Duration: 7 Days
FIFO / Recycle mode: Off
Input Calibration
Setup Values
1 Vln 480 Volts = 480.0
2 Il 400 Amps = 400.0
3 V2 480 Volts = 480.0
4 I2 400 Amps = 400.0
5 Vne 480 Volts = 480.0
6 I3 400 Amps = 400.0
Alarms
: On
Alarm Values High Low
1 Vac 253.0 216.2
3 % 8.0 Off
7 Pst 1.00 Off
8 Plt 0.80 Off
16 Hz 50.50 49.50
Hook Up
: Single Phase
Channel Functions
Input Channels
1 Vln 0 to 480 Vac
2 Il 0 to 400 Aac (Rogowski)
3 V2 0 to 480 Vac
4 I2 0 to 400 Aac (Rogowski)
5 Vne 0 to 480 Vac
6 I3 0 to 400 Aac (Rogowski)
Detailed (Math) Channels
1 RMS of Signal Vln (Vac)
2 RMS of Signal Ia (Aac)
3 % THD Traditional of Signal Van (%)
4 Value all Harmonics of Signal Ia (Aac)
5 Flicker sensation on Van (Pfs)
6 Flicker flag on Van (Flg)
7 Flicker short term Van 10 mins (Pst)
8 Flicker long term Van 2 hours (Plt)
9 RMS of Signal Vne (Hi resolution) (Vac)
10-15 Unspecified
16 AC Frequency (Hz)