12
Location 137: Programming The Secondary Exit Delay (Zone Type 7)
Location 137 contains the number of 10 second increments after arming, before zone trips will be recognized on a
zone type 7. The exit delay can be programmed in 10 second increments from 10 to 150 seconds ("1" = 10 seconds
through "15" = 150 seconds). For example, programming a "2" in this location will produce an exit delay of 20
seconds. (Note: A "0" entry is treated as zero (0) seconds). Programming a "6" in this location will produce an exit
delay of 60 seconds. If the exit delay time in this location is less than, or equal to that in location 135, zone type 7
will be delayed the amount of time programmed in location 135.
Location 138: Programming The Siren Shutdown/Recycle Timeout
Location 138 contains the number of 2 minute increments in the automatic cutoff time. The automatic cutoff time can
be programmed in 2 minute increments from 2 to 30 minutes ("1" = 2 minutes through "15" = 30 minutes). For
example, programming a "2" in this location will produce an automatic cutoff time of 4 minutes. Programming a "6"
in this location will produce an automatic cutoff time of 12 minutes.
Locations 139-154: Programming The Zone Types For Zones 1-16
Locations 139 through 154 contain a number identifying the characteristics of zones 1 through 16. Location 139
corresponds to zone 1 and location 154 corresponds to zone 16. These zones have been factory defaulted to the
zone type shown in the below chart. Other zone characteristics can be found in the table on the following page.
ZONE #
DEFAULT CHARACTERISTICS
1
"3" = ENTRY/EXIT DELAY ZONE
2
"5" = INTERIOR FOLLOWER
3-16
"6" = INSTANT
DATA
AVAILABLE ZONE TYPES
"1"
DAY ZONE
- When armed, a trip produces an instant alarm. When disarmed, a trip activates
the keypad sounder.
"2"
24 HOUR
- A trip on a 24 Hour zone produces an instant alarm when armed or disarmed.
"3"
ENTRY/EXIT
- A trip will start entry delay. The lack of a trip during exit delay will enable the
Automatic Bypass or Instant mode if so programmed.
"4"
INTERIOR DELAY
- A trip on Interior Delay zone will initiate an entry delay. It will be ignored
during exit delay and when disarmed .
"5"
INTERIOR FOLLOWER
- Interior zone that follows the delay zones. It is instant during
non-delay times. It can be bypassed before arming, or by allowing it to automatically be
bypassed in the Automatic Bypass/Instant mode if so programmed.
"6"
INSTANT
- Produces an instant alarm if tripped when armed. Ignored when disarmed.
"7"
SECONDARY DELAY
- Like an Entry/Exit zone but has its own independent delay time.
"8"
FIRE
(PRIORITY WHEN AHJ HAS NOT APPROVED) - A short on a FIRE zone (non-
bypassable) will communicate to the central station when the Ranger 9000E is armed or
disarmed. An open will create a Trouble condition. Keypad LED will be steady for FIRE, and
flashing for Trouble.
"9"
KEYSWITCH
- A zone attached to a momentary keyswitch will cause the Ranger 9000E to arm
or disarm when the zone is shorted. NOTE: Program the corresponding "Special Characteristics
For Zones 1-16"(locations 155-170)as a "0".