30
INSTALLATION
Check the appliance is electrically safe when you have finished.
ArtNo.130-0010 Electrical connections single-phase
L
N
230 V ac 50 Hz
10 mm² max
6 mm² max
Current Operated Earth Leakage Breakers
The combined use of your induction cooker and other
domestic appliances may cause nuisance tripping, so we
recommend that the cooker is protected on an individual
RCD (Residual Current Device) or RCBO (Residual Current
Breaker with Overload).
IF IN DOUBT, PLEASE CONSULT A SUITABLY QUALIFIED
ELECTRICIAN.
L1
N
L3
L2
3N ac
230/400 V 50 Hz
6 mm² max
10 mm² max
6 mm² max
Electrical Connection
The cooker must be installed by a qualified electrician, in
accordance with all relevant British Standards/Codes of
Practice (in particular BS 7671), or with the relevant national
and local regulations.
The cable size and type should be suitable for the
Electrical Load of the appliance and comply with the local
requirements as defined in the latest editions of BS 7671 and
or BS EN 50565-1 Reference B4.
n
n
WARNING: THE APPLIANCE MUST BE EARTHED.
NOTE
: The cooker must be connected to the correct electrical
supply as stated on the voltage label on the cooker, through
a suitable cooker control unit incorporating a double-pole
switch, having a contact separation of at least 3 mm in all
poles.
n
n
The cooker MUST NOT be connected to an ordinary
domestic power point.
Access to the mains terminal is gained by removing the
electrical terminal cover box on the back panel. Connect
the mains cable to the correct terminals for your electrical
supply type (
). Check that the links are
correctly fitted and that the terminal screws are tight.
Secure the mains cable using the cable clamp.
Final Checks
Hob Check
Check each cooking zone in turn. Be sure to use pans of the
correct size and material.
Grill Check
Turn on the grill control and check that the grill heats up.
Oven Check
Set the clock as described earlier, and then turn on the ovens.
Check the oven fans start to turn and that the ovens heat up.
Fig. 9.11
Fig. 9.12