Randell 9000-290 Series Operator'S Manual Download Page 4

OM-9000-290 SERIES REFRIGERATORS/FREEZERS

SERVICE

CAUTION:  COMPONENT PARTS SHALL BE REPLACED WITH FACTORY OEM PARTS. 

SERVICE WORK SHALL BE DONE BY FACTORY AUTHORIZED SERVICE 

PERSONNEL, SO AS TO MINIMIZE THE RISK OF POSSIBLE IGNITION DUE TO 

INCORRECT PARTS OR IMPROPER SERVICE.

CAUTION:  BEFORE MAKING ANY REPAIRS,  ENSURE THE UNIT IS DISCONNECTED  

FROM ITS POWER SOURCE.

This piece of equipment uses a R290 Refrigeration system.  This equipment has 
been clearly marked on the serial tag the type of refrigerant that is being used.   
There is also a warning labels stating that the unit contains R290 refrigerant. R290 
is safe to use as long as you follow these warning labels and some.  
No smoking or open flames when servicing this equipment.  If needed, use a CO2 
or dry=power type fire extinguisher
Replacement parts used on any R290 Refrigeration system cabinet must have 
specific UL certification for non-sparking components. 
Only authorized service technician, certified in R290 system should service this 
equipment.

MANIFOLD SET

A R134A manifold set can be used for servicing this equipment.  

REFRIGERANT RECOVERY

Follow all national and local regulations for R-290 refrigerant recovery.  

LEAKING CHECKING AND REPAIR

Leak check an R-290 system the same way you would an R-134a or R-404A 
system with the following exceptions. 
1.  Do not use a Halid leak detector on a R290 system.
2.  Electronic leak detector must be designated specifically for combustible gas.
Use of a bubble solution or an ultrasonic leak detector are acceptable.   
When repairing a leak, it is recommended using oxygen free dry nitrogen with a 
trace gas not exceeding 200PSI. 
When accessing an R290 system, piercing valves are not to remain on the 
equipment in a permanent manner. After charge is recovered, Schrader valves 
are to be installed on the process stubs.  Proper charge is to be weighed into the 
system and the system is to be leak checked afterwards.
The R290 equipment must have red process tubes and other devices through 
which the refrigerant is serviced, such as any service port.  This color marking 
must remain on the equipment.  If marking is removed, it must be replace and 
extend at least 2.5 centimeters (1”) from the compressor.

CHARGING

Follow the charge amount specified on the data tag.  It is recommended to use the 
shortest hoses possible to prevent undercharging.
•  Ensure the system is sealed and leak checked 
•  Evacuate system to a minimum 500 micron
•  Weigh in correct charge
•  Leak check the system again
•  Bleed the refrigerant from the high side hose to the low side hose
•  Disconnect the hoses
•  Remove line taps

TROUBLESHOOTING

This unit is designed to operate smoothly and efficiently if properly maintained. 
However, the following is a list of checks to make in the event of a problem. Wir-
ing diagrams are found at the end of this manual. When in doubt, turn unit off 
and contact service at 888-994-7636 or [email protected].

SYMPTOM

POSSIBLE CAUSE

PROCEDURE

Unit does not run

No power to unit

Plug in unit

Control in OFF position

Turn controller on

Faulty control

Call for service at 888-994-
7636

Unit too cold

Incorrect set point

Adjust control set point

Unit too warm

Door / drawer ajar

Ensure door / drawer is fully 
closed

Gasket torn or out of place

Inspect the gasket for wear 
and position

Incorrect set point

Adjust control set point

Warm product introduced 
to cabinet

Pre-chill product 37ºF or 3ºF 
degree for freezer 

Ice on the coil

Initiate manual defrost

Unit noisy

Ice on the coil

Initiate manual defrost

Unit does not defrost Excessive ice on the coil

Initiate manual defrost

Summary of Contents for 9000-290 Series

Page 1: ...commend that you do so at once Manufacture Service Questions 888 994 7636 RETAIN THIS MANUAL FOR FUTURE REFERENCE NOTICE Due to a continuous program of product improvement Unified Brands reserves the...

Page 2: ...ble for damage to equipment if improperly installed 4 Allow unit time to cool down to temperature If temperature adjustments are required the control is located on the front panel Confirm that the uni...

Page 3: ...ensing unit and evaporator assembly 2 Clean all gaskets on a weekly if not daily basis with a solution of warm water and a mild detergent to extend gasket life 3 Lubricate door hinges with lithium gre...

Page 4: ...ot to remain on the equipment in a permanent manner After charge is recovered Schrader valves are to be installed on the process stubs Proper charge is to be weighed into the system and the system is...

Page 5: ...2 X X X 1 RP DOR108 DOOR LEFT 32 X X X 2 RP HNG026 HINGE STRAP L BRACKET BOTTOM X X X X X X X X X X X X X X X X X 3 RP HNG9901 HINGE ASSY SELF CLOSING RIGHT X X X X X X X X X X X X X X X X X 3 RP HNG9...

Page 6: ...X X X 4 RF FLT9902 WASHER 5 16 FLAT X X X X X X X X X X X X X X X X X 5 RF WRP1705 HEAT EXCHANGE X X X 5 RF WRP1706 HEAT EXCHANGE X 5 RF WRP1707 HEAT EXCHANGE 8 2017 X X X 6 RP SHD1709 SHROUD CONDENSO...

Page 7: ...F 290 SHROUD EVAPORATOR X X X X X X X X X X X X 2 T06 0561G 290 SHROUD EVAPORATOR X 3 RF COI120B COIL EVAPORATOR X X X X X X X X X X X X X X X X X 4 EL WIR1501 POWER CORD 9 X X X X 4 EL WIR0106 POWER...

Page 8: ...2 RP TOP9301 TOP ASSY REPLACEMENT X 2 RP TOP9602 TOP ASSY REPLACEMENT X 2 RP TOP9604 TOP ASSY REPLACEMENT X 3 HD CST060 CASTER X X X X X X X X X 3 HD CST061 CASTER X X X X X X X X X 3 HD CST025 CASTER...

Page 9: ...REPLACEMENT X 3 HD CST060 CASTER X X X X X 3 HD CST061 CASTER X X X X X 3 HD CST025 CASTER X 4 RP CPN1703 PAN CONDENSATE 4 RP CPN1705 PAN CONDENSATE X X X X X 4 RP CPN1707 PAN CONDENSATE 08 2017 4 RP...

Page 10: ...404F 290 9404F 32 290 9802F 290 9302F 290 9401 290 9412 32 290 9801 290 9303 290 9305 290 9601 290 ITEM SERVICE PART DESCRIPTION 1 RP BCK1704 BACK PANEL SS X X X 1 RP BCK1705 BACK PANEL SS X X X 1 RP...

Page 11: ...2 ROLL COVER FRONT 8 PAN X X 2 RP ROL1110 ROLL COVER FRONT 12 PAN X 3 HD PIN0101 LOCATING PIN X X X X X 4 FA NUT0403SS FASTENER ACORN NUT X X X X X 5 RQ ROL9412 HOOD COVER ASSEMBLY X 6 RP LID028 HOOD...

Page 12: ...12 OM 9000 290 SERIES REFRIGERATORS FREEZERS Wiring Diagram...

Page 13: ...13 OM 9000 290 SERIES REFRIGERATORS FREEZERS Wiring Diagram...

Page 14: ...14 OM 9000 290 SERIES REFRIGERATORS FREEZERS Wiring Diagram...

Page 15: ...15 OM 9000 290 SERIES REFRIGERATORS FREEZERS Wiring Diagram...

Page 16: ...OM 9000 290 SERIES REFRIGERATORS FREEZERS Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed...

Reviews: