EXTENDING SENSOR

CAUTION: Sensor wiring splices may be made external from the control. 
CAUTION: Disconnect power to control before wiring to avoid possible 

electrical shock or damage to the controller.
Additional cable can be spliced to the sensor cable to increase the 

length beyond the standard 8 feet. It can be extended up to 400 feet. 

The cable should be at least 22 AWG or larger to keep additional  

resistance to a minimum.
All splices and wire lengths added to the sensor cable should be made 

according to acceptable wiring practices and should conform to the 

National Electrical Code and local regulations. Use copper conductors 

only. Shielded cable is not required. The sensor is not polarity sensitive.     

Checkout Procedure

1.   Before applying power, make sure installation and wiring  

connections are correct.

2.   Apply power to the control and observe one or more cycles  

of operation.

3.   If performance indicates a problem, check sensor resistance 

to determine if sensor or control is at fault.

4.   To check sensor resistance, disconnect sensor and measure 

the resistance across the leads while measuring temperature  

at the sensor.

SENSOR REPLACEMENT

Figure 9: Sensor replacement on Display (Upper) Circuit Board.

Sensor Replacement

ETC models are available with Quick Connect Sensor feature that 

allows for easy sensor replacement due to damage or wear. To access 

the sensor connector, disconnect the power supply and open the 

control. Remove single screw located in the center of the Display 

Upper Circuit Board and carefully remove Display Board Circuit. 

Remove Sensor Strain Relief to allow  sensor to be removed from unit. 

See Figure 5 for location of sensor strain relief. The sensor connection 

is made at the P1 Connector on the Display Upper Circuit Board.  

See figure 9 for connection information.

Replacement Sensor - Order

 

Uni-Line Number 1309007-044

 

(OEM Number 1309007-048)

Figure 10

SPECIFICATIONS

The sensor is a negative temperature coefficient (NTC) thermistor 

sensor. The sensor resistance decreases with temperature increase. 

It is .25 x 1.94 long with 8 feet #22 AWG cable. The thermistor has a 

reference resistance of 30,000 ohms at 77°F (25°C).

Deg. C.

Deg. F.

RES. Nom.

-40

-40

1,010,000

-30

-22

531,000

-20

-4

291,200

-10

14

166,000

0

32

97,960

10

50

59,700

20

68

37,470

25

77

30,000

30

86

24,170

40

104

15,980

50

122

10,810

60

140

7,464

70

158

5,200

80

176

3,774

90

194

2,753

100

212

2,036

110

230

1,531

Figure 11:

Resistance vs Temperature

 

Sensor including 8 foot cable.

SENSOR CONNECTOR

Summary of Contents for ETC Series

Page 1: ...y Electrical Ratings NO Contact 120V 208 240V Full load amps 9 8 Amps 4 9 Amps Locked rotor amps 58 8 Amps 29 4 Amps Resistive amps 9 8 Amps 4 9 Amps Horsepower 1 2 HP 1 2 HP NC Contact Full load amps 5 8 Amps 2 9 Amps Locked rotor amps 34 8 Amps 17 4 Amps Resistive amps 5 8 Amps 2 9 Amps Horsepower 1 4 HP 1 4 HP Pilot Duty 125 VA at 120 208 240 VAC Control Ambient Temperature Operating 20 F to 14...

Page 2: ...s the SET key again to access the stage 1 cooling or heating mode The LCD will display the current mode either C1 for cooling or H1 for heating Then press either the up Ç or down È key to toggle between the C1 or H1 designation Step 5 Press the SET key again to access the Anti short Cycle Compressor Delay when in Cooling Mode Press the up Ç or down È keys to set the delay from 1 to 20 minutes Pres...

Page 3: ...trôleur ETC NE PAS rétablir l alimentation élec trique de l appareil avant que le contrôleur ETC ne soit correctement installé et que le couvercle ne soit assemblé Risque d incendie Ne pas placer le contrôleur ETC dans une atmosphère explosive car un incendie pourrait être déclenché par d éventuelles étincelles survenant dans le contrôleur Toutes les commandes de l ETC sont conçues pour contrôler ...

Page 4: ...regulations and ordinances including without any limitation all requirements imposed under the National Electric Code and any applicable building codes PRÉCAUTIONS Lire toutes les informations contenues dans ces instructions avant d installer ou d utiliser le contrôleur ETC Les schémas et toutes les autres informations figurant dans ces instructions d installation sont indiqués à des fins d illust...

Page 5: ... representation of the sensor temperature with 0 volts 30 F and 10 volts 220 F See figure 8 for wiring information and Figure 5 for location of the entry hole The reference for this output is designated by the symbol on the wiring diagram The output signal is designated by the symbol Figure 8 0 10 V Analog Output Located on Power Lower Circuit Board Figure 7 Typical Wiring Diagram for 24 VAC Power...

Page 6: ... a problem check sensor resistance to determine if sensor or control is at fault 4 To check sensor resistance disconnect sensor and measure the resistance across the leads while measuring temperature at the sensor SENSOR REPLACEMENT Figure 9 Sensor replacement on Display Upper Circuit Board Sensor Replacement ETC models are available with Quick Connect Sensor feature that allows for easy sensor re...