Ranco ETC-111000 Quick Start Manual Download Page 1

D71

ETC COMMERCIAL TEMPERATURE CONTROLS

RANCO ETC 
COMMERCIAL
TEMPERATURE 
CONTROLS

The Ranco ETC is a microprocessor-based family of temperature controls
designed to provide on/off control for commercial heating, cooling, air condi-
tioning and refrigeration applications. With its wide temperature range, one
and two stage capability, selectable heating/cooling modes and multi-voltage
input, the ETC is one of the most versatile temperature controls available.

DIGITAL DISPLAY

Unlike many electronic controls, the ETC is simple to install and set up. One
finger is all you need to program it. The standard digital display and keypad
allow the user to adjust the temperature settings with 1° resolution. Setpoint
temperature, differential and mode of operation (heating or cooling) can all be
selected using the keypad and display.

When not in the programming mode, the display gives a constant readout of
the sensor temperature. Annunciators on the liquid crystal display also indi-
cate when the relay is energized.

CHOICE OF ONE OR TWO STAGE MODELS

The ETC line includes both one and two stage models. On two stage con-
trols, each stage can be set independently thus eliminating the bothersome
task of calculating interstage temperatures. And two stage models can be set
up with overlapping heating or cooling stages.

REMOTE TEMPERATURE SENSING

The ETC is capable of remote temperature sensing up to 400 feet away from
the control when using standard 22 gauge sensor wire.

BUILT-IN SAFETY

Every ETC model is equipped with diagnostic programs that check for hard-
ware, software or system problems and display different error codes to indi-
cate where the trouble is.

The ETC also has a keypad lockout switch to prevent tampering with the
control settings by unauthorized personnel. The switch, which is located
inside the enclosure, can be used to disable the keypad function.

OPTIONAL ANALOG OUTPUT

ETC models are available with a 0 to 10 volt analog output that can be used
for remote temperature indication or as input to a central monitoring system.
This signal is a linear representation of the sensor temperature with 0 volt
–30°F and 10 volts = 220°F.

ETC-111000

SPECIFICATIONS

Temperature setpoint range

–30° to 220°F

Differential range

1°F to 30°F

Input power requirements

120 or 208/240 VAC (24 VAC optional)

Sensor

Thermistor, 2" long x 1/4" dia. with 8' cable

Control Ambient Temperatures

Operating

–20°F to 140°F

Storage

–40°F to 176°F

Ambient humidity

0 to 95% RH, non-condensing

Enclosure

NEMA 1, plastic (NEMA 4X optional)

Dimensions

NEMA 1 models, 6.52" high x 2.7" wide x 2.48" deep

NEMA 4X models, 7.84" high x 2.7" wide x 2.48" deep

0 to 10 V output impedance

1 K ohms

Agency Approvals

UL listed, file E94419, Guide XAPX

CSA certified, file LR68340. class 4813 02

Switch action

SPDT

RELAY OUTPUT RATINGS - NO (NC):

ONE STAGE

TWO STAGE

120V

208/240V

120V

208/240V

Full load amps

16 (5.8) A

8 (2.9) A

9.8 (5.8) A

4.0 (2.9) A

Locked rotor amps

96 (34.8) A

48 (17.4) A

58.8 (34.8) A

29.4 (17.4) A

Resistive amps

15 (5.8) A

8  (2.9) A

9.8 (5.8) A

4.9 (2.9) A

Horsepower

1 (1/4) HP

1 (1/4) HP

1/2 (1/4) HP

1/2 (1/4) HP

Pilot duty

125VA at 120/208/240 VAC

ORDERING DATA

UNI-LINE

NUMBER

INPUT

0 TO 10 VOLT

ORDER NO.

OF STAGES

ENCLOSURE

VOLTAGE

OUTPUT

ETC-111000

NO

ETC-111100

YES

ETC-112000

NO

ETC-112100

YES

ETC-141000

NEMA 4

NO

ETC-211000

ETC-211100

YES

ETC-212000

NO

ETC-212100

YES

ETC-241000

NEMA 4

120/208/240 VAC

NO

ONE

TWO

NEMA 1

NEMA 1

120/208/240 VAC

120/208/240 VAC

24 VAC

24 VAC

NO

Summary of Contents for ETC-111000

Page 1: ...codes to indi cate where the trouble is The ETC also has a keypad lockout switch to prevent tampering with the control settings by unauthorized personnel The switch which is located inside the enclosure can be used to disable the keypad function OPTIONAL ANALOG OUTPUT ETC models are available with a 0 to 10 volt analog output that can be used for remote temperature indication or as input to a cent...

Page 2: ...20or 208 240 VAC 24 VAC optional 50160 Hz 30 t0220 1 Fto 30 F SPOT Thermistor 1 94 in long x 0 25 in diameterwith 8 ft cable 120 208 240VAC 100 Milliamps 24 VAC 2 6 VA Relay Electrical Ratings 120V 20S 240V NO Contact Full load amps 16A 8A Locked rotor amps 96A 48A Resistive amps 15A 8A Horsepower 1 hp 1 hp NC Contact Full load amps 5 8A 2 9A Locked rotor amps 34 8 A 17 4 A Resistive amps 5 8A 2 9...

Page 3: ... control settings are retained in non volatile memory if power to ETC is interrupted for any reason Re programming is not necessary after power outages or disconnects unless different control settings are required Lockout Switch The ETC is provided with a lockout switch to prevent tampering by unautho rized personnel When placed inthe LOCK position the keypad isdisabled and nochanges to the settin...

Page 4: ...sphere 4 Ranco ErC controls have been approved by Underwriter s Laboratories as UL listed however approval does not extend to their use for any otherpurpose Ranco assumes no responsibility for any unconventional application of its control unless such application has been approved in writing by Ranco 5 It is the responsibility of the installer and the user to assure that his or its application and ...

Page 5: ...se Refer to figure 3 for location of the entry hole FlQure 7 for wiring Analog Output ETG models are available with an optional 0 to 10 volt analog output This signal is a linear representation of the sensor temperature with 0volts 30 F and 10 volts 220 F See figure 8 for wiring information and figure 3 for location of the entry hole The reference for this output is designated by the symbol on the...

Page 6: ...equires the sensor to be in good contact with the surface being re il m Vt lh u Vtffi rffi Vl omrm J senslng 1m 143 158 176 194 212 230 10 810 7 464 5 200 3 774 2 753 2 036 1 531 Ranco North America 8115 U S Rt 42 North Plain City Ohio 43064 Figure 10 Resistance vs Temperature of 1309007 044 Sensor including 8 foot cable An Invensys Company ...

Page 7: ...ose of illustration andgeoern l reference only Ranco assumes no responsibility for any uncooventionaJ application of this control unless such application has been approved in writing by Ranco Deg c Deg F RES Nom 40 40 1 010 000 30 22 531 000 20 4 291 200 10 14 166 000 0 32 97 960 10 50 59 700 20 68 37 470 25 77 30 000 30 86 24 170 40 104 15 980 50 122 10 810 60 140 7 464 70 158 5 200 80 176 3 774 ...

Reviews: