Select “Vac Set”. The menu below is now shown.
•
The current vacuum level is indicated in the top field.
•
Notice the number of units currently running on the bottom of the screen. If more than 1 unit is
running, use the "-" button to adjust the “Low Set point” value so that it is several inches Hg
lower than the Current Vacuum level and then select “Save”.
•
IMPORTANT
: Verify the number of units now running is 1.
•
After verifying that only 1 unit is running, use the "+" and "-" buttons to adjust the "Low Set
point" to 1” Hg less than the “Current Vacuum” level. For example if the “Current Vacuum”
level is 8.5” Hg, the low set point value should be 7.5” Hg.
•
Select “Save” and then “Back” to return to the “System Setup” screen. Select “Home”.
OWL Programming is now complete.