Convection area above the stove on
instillation
must be minimum
700cm²
the area can be distributed over
several holes.
Convection area below the stove on
instillation
Must be minimum
530cm²
the area can be distributed over
several holes.
Convection
There is a minimum requirement for the convection
area. This area must be
observed due to danger of overheating and due to distance to flammable
materials. Make sure that the stove can pull convection air in under the stove.
And lead it back out of the stove.
When installed in a completely non-flammable construction, there are no
requirements for convection area but it is recommended to transfer the area
from the panel construction as the brick work may crack at high tempera-
tures.