background image

 

Rais Bionic Fire Manual 

January 2014 

Chimney 

For the stove to perform satisfactorily the chimney height must be sufficient to ensure an adequate draught of 
approximately 15 Pa so as to clear the products of combustion and prevent smoke problems into the room.  
 
NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the 
top of the chimney should be satisfactory. Alternatively the calculation procedure given in EN 13384-1 may 
be used as the basis for deciding whether a particular chimney design will provide sufficient draught. 
 
The outlet from the chimney should be above the roof of the building in accordance with the provisions of 
Building Regulations Approved Document J. 
 
If installation is into an existing chimney then it must be sound and have no cracks or other faults which might 
allow fumes into the house. Older properties, especially, may have chimney faults or the cross     section may 
be too large i.e. more than 230 mm x 230 mm. Remedial action should be taken, if required, seeking expert 
advice, if necessary. If it is found necessary to line the chimney then a flue liner suitable for solid fuel must be 
used in accordance with Building Regulations Approved Document J. 
 
Any existing chimney must be clear of obstruction and have been swept clean immediately before             
installation of the stove. If the stove is fitted in place of an open fire then the chimney should be swept one 
month after installation to clear any soot falls which may have occurred due to the difference in combustion 
between the stove and the open fire. 
 
If there is no existing chimney then either a prefabricated block chimney in accordance with Building       
Regulations Approved Document J or a twin walled insulated stainless steel flue to BS 4543 can be used. 
These chimneys must be fitted in accordance with the manufacturer’s instructions and Building              
Regulations. 
 
A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not suitable for using for 
the complete chimney. The chimney and connecting fluepipe must have a minimum diameter of 150 mm and 
its dimension should be not less than the size of the outlet socket of the stove. 
 
Any bend in the chimney or connecting fluepipe should not exceed 45°.  90° bends should not be used. 
 
Combustible material should not be located where the heat dissipating through the walls of fireplaces or flues 
could ignite it. Therefore when installing the stove in the presence of combustible materials due  account 
must be taken of the guidance on the separation of combustible material given in Building  Regulations     
Approved Document J and also in these stove instructions. 
 
If it is found that there is excessive draught in the chimney then a draught stabiliser should be fitted. Fitting of 
a draught stabiliser will affect the requirement for the permanent air supply into the room in which the stove is 
fitted in accordance with Approved Document J (see also combustion air supply). 
 
Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and 
connecting fluepipe where it is not intended for the chimney to be swept through the appliance, also to permit 
visual checks on the integrity of the flue when the appliance is serviced. 

 
Hearth 

The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not   
independently supported. The weight of the stove is indicated in the brochure. 
 
The stove should always be installed on a non-combustible hearth of a size and construction that is in      
accordance with the provisions of the current Building Regulations Approved Document J. 
 
The clearance distances to combustible material beneath, surrounding or upon the hearth and walls         
adjacent to the hearth should comply with the guidance on the separation of combustible material given in 
Building Regulations Approved Document J and also in these stove instructions. 
 

If the stove is to be installed on a combustible floor surface, it must be covered with a non-
combustible material at least 12mm thick, in accordance with Building Regulations           
Approved Document J, to a distance of 30 cm in front of the stove and 15 cm to each side 
measuring from the door of the combustion chamber 

 

Summary of Contents for BIONIC FIRE

Page 1: ...FIRE IMPORTANT INFORMATION On first lighting the stove you must be careful not to touch the painted surfaces and it is MOST IMPORTANT that the door is kept slightly ajar in order for the door seal an...

Page 2: ...2 Rais Bionic Fire Manual January 2014...

Page 3: ...ER SETTING 18 CORNER SETTING 45 19 INSTALLATION DISTANCE FROM NON COMBUSTIBLE WALL 20 FOR THE INSTALLER 21 OPERATING INSTRUCTIONS 21 FUEL 21 DRYING AND STORAGE 22 ROOM VENTILATION AND STOVES 22 STOVE...

Page 4: ...water Asbestos This stove contains no asbestos If there is a possibility of disturbing any asbestos in the course of installation then please seek specialist guidance and use appropriate protective e...

Page 5: ...te chimney The chimney and connecting fluepipe must have a minimum diameter of 150 mm and its dimension should be not less than the size of the outlet socket of the stove Any bend in the chimney or co...

Page 6: ...during the installation of this appliance must be carried out by a registered competent electrician and in accordance with the requirements of the latest issue of BS 7671 Carbon Monoxide Alarm A carbo...

Page 7: ...appliance If the alarm sounds unexpectedly follow the instructions given under Warning Note above Use of fireguard When using the stove in situations where children aged and or infirm persons are pres...

Page 8: ...ng can cause ex cess smoke See Page 9 for Refuelling details Operation with door left open Operation with the door open can cause excess smoke The appliance must not be operated with the appliance doo...

Page 9: ...low fuel to spill over the top of the front fire bars Take care that fuel does not project over the front fire bars or damage to the glass may be caused when the doors are closed Flueway cleaning It i...

Page 10: ...10 Rais Bionic Fire Manual January 2014...

Page 11: ...11 Rais Bionic Fire Manual January 2014...

Page 12: ...12 Rais Bionic Fire Manual January 2014...

Page 13: ...13 Rais Bionic Fire Manual January 2014...

Page 14: ...14 Rais Bionic Fire Manual January 2014...

Page 15: ...15 Rais Bionic Fire Manual January 2014...

Page 16: ...16 Rais Bionic Fire Manual January 2014...

Page 17: ...17 Rais Bionic Fire Manual January 2014...

Page 18: ...18 Rais Bionic Fire Manual January 2014...

Page 19: ...19 Rais Bionic Fire Manual January 2014...

Page 20: ...20 Rais Bionic Fire Manual January 2014...

Page 21: ...21 Rais Bionic Fire Manual January 2014...

Page 22: ...22 Rais Bionic Fire Manual January 2014...

Page 23: ...23 Rais Bionic Fire Manual January 2014...

Page 24: ...24 Rais Bionic Fire Manual January 2014...

Page 25: ...25 Rais Bionic Fire Manual January 2014...

Page 26: ...26 Rais Bionic Fire Manual January 2014...

Page 27: ...27 Rais Bionic Fire Manual January 2014...

Page 28: ...28 Rais Bionic Fire Manual January 2014...

Page 29: ...29 Rais Bionic Fire Manual January 2014...

Page 30: ...30 Rais Bionic Fire Manual January 2014...

Page 31: ...31 Rais Bionic Fire Manual January 2014...

Page 32: ...32 Rais Bionic Fire Manual January 2014...

Page 33: ...33 Rais Bionic Fire Manual January 2014 Spare Parts...

Page 34: ...34 Rais Bionic Fire Manual January 2014...

Page 35: ...35 Rais Bionic Fire Manual January 2014 Accessories 00065172290 Rear air system connection 0065172390 Bottom air system connection...

Page 36: ...36 Rais Bionic Fire Manual January 2014...

Page 37: ...37 Rais Bionic Fire Manual January 2014...

Page 38: ...38 Rais Bionic Fire Manual January 2014...

Page 39: ...39 Rais Bionic Fire Manual January 2014...

Page 40: ...Bionic Fire Manual January 2014 U K Distributor Robeys Ltd Riverside Goods Road Belper Derbyshire England DE56 1UU Tel 01773 820940 Fax 01773 820477 E Mail info robeys co uk www robeys co uk Septembe...

Reviews: