RAIS attika VISIO UNIQ Installation Manual Download Page 4

EN

3 - EN

INSTALLATION INSTRUCTIONS

Thank you for choosing your new RAIS or 

ATTIKA product! This installation instructions 

manual will ensure that your fireplace insert 

is installed correctly and that it will provide 

you with comfort and pleasure for many 

years to come. 

GENERAL INFORMATION

It is important to correctly install the 

fireplace insert out of consideration for both 

the environment and personal safety.

The installation must comply with all local 

rules and regulations, including those that 

refer to national and European standards. 

A certified chimney sweeper should be 

contacted before set-up.

No unauthorised alterations may be made to 

the fireplace insert.

GENERAL INSTALLATION REQUIREMENTS

Before the fireplace insert may be put to use, 

the set-up must be reported to your local 

chimney sweeper.

There must be a plentiful supply of fresh air 

into the room where the insert is placed to 

ensure good combustion, possibly through 

an AirSystem connection. Be aware that 

any mechanical air extraction, for example 

a cooker hood, can reduce the supply of air. 

Any air vent must be positioned in a way that 

ensures the supply of air cannot be blocked. 

The air consumption of the fireplace insert is 

32 m

3

/h.

The floor structure must be able to support 

the weight of the fireplace insert and a 

chimney, if required. If the existing floor 

structure does not meet this requirement, 

suitable measures must be taken (e.g. 

installation of a load distribution plate). If in 

doubt, contact a building expert.

National and local regulations must be 

complied with, including the size of the 

non-flammable plate that must cover the 

flammable floor in front of the fireplace insert 

to protect the floor from falling embers. 

The fireplace insert must be positioned at a 

safe distance from flammable material. Due 

to risk of fire, flammable items (e.g. furniture) 

may not be positioned closer to the insert 

than specified in the sections on placement. 

When deciding where to install your RAIS/

ATTIKA fireplace insert, you should consider 

being able to heat other rooms in your home 

to get the most out of your new fireplace 

insert.

After receiving your fireplace insert, please 

check it for any defects.

CHIMNEY

The chimney must be tall enough to ensure 

correct draught conditions, i.e. -12 pascal 

to -18 pascal. If the recommended chimney 

draught cannot be achieved, problems of 

smoke puffing from the door may arise 

when heating. We recommend adapting the 

chimney to the flue pipe collar. The collar is 

200 mm in diameter.

If the draught is too strong, it is advisable to 

equip the chimney with a regulating damper. 

If a regulating damper is fitted, you must 

ensure that there is a free flow-through 

area of at least 20 cm² when the regulating 

damper is closed. 

Remember: there must be unobstructed 

access to the access door on the chimney.

The length of the chimney, calculated from 

the top of the fireplace insert should not 

be less than 3 metres and must be at least 

80 cm above the roof ridge. If the chimney 

is placed on the side of the house, the top of 

the chimney must never be lower than the 

roof ridge or the roof’s highest point.

Note that there are often national and local 

regulations relating to houses with thatched 

roofs.

The fireplace insert is suitable for being 

connected to a shared flue, but we 

recommend that the feed-ins are positioned 

to maintain a clearance-level difference of at 

least 250 mm between them. 

INSTALLATION INSTRUCTIONS

Note!

RAIS/ATTIKA recommends having the in-

sert installed by an authorised technician. 

Please ask your dealer for further informa-

tion.   

Summary of Contents for attika VISIO UNIQ

Page 1: ...O UNIQ DK INSTALLATIONSVEJLEDNING DE INSTALLATIONSANLEITUNG EN INSTALLATION GUIDE FR NOTICE D INSTALLATION NO INSTALLASJONSVEILEDNING SE INSTALLATIONSANVISNING FIN ASENNUSOHJEET NL INSTALLATIEHANDLEID...

Page 2: ...EN 1 EN SERIAL NUMBER MUST BE PLACED HERE...

Page 3: ...tions 8 Norway specific instructions 9 Transport safety fittings 10 Reflective insulation panel 11 Choice of material for installation 13 Installation dimensions 15 Placement distances 16 Heat distrib...

Page 4: ...he floor from falling embers The fireplace insert must be positioned at a safe distance from flammable material Due to risk of fire flammable items e g furniture may not be positioned closer to the in...

Page 5: ...H mm 482 X 279 X 250 Min flue draught pascal 12 Weight kg min depending on the model 268 Efficiency 78 CO emission attributed to 13 O2 0 0714 893 mg Nm NOx emission attributed to 13 O2 mg Nm 113 OGC e...

Page 6: ...12 n198 n198 1465 632 0 139 414 926 1398 1525 292 445 445 n149 159 4 364 5 428 691 500 512 891 891 445 632 143 512 n198 n198 1465 632 0 139 414 926 1398 1525 R149 292 445 445 n149 159 445 445 364 5 42...

Page 7: ...the installation and operating instruction manual Intermittent operation F Veuillez lire et observer les instructions du mode d emploi Foyer dur e de combustion limit e homologu pour chemin e connexi...

Page 8: ...be removed DISPOSAL RECYCLING OF PACKAGING The fireplace insert is delivered in recyclable pack aging This packaging must be disposed of in ac cordance with national regulations relating to the dispos...

Page 9: ...r in the flue Before Visio Uniq may be installed in a smoke controlled area of the UK a stopper must be installed This will prevent the flue from closing entirely This is done by setting the flue hand...

Page 10: ...f a mechanical stopper in the flue Before Visio Uniq may be installed in Norway a stopper must be installed This will pre vent the flue from closing entirely This is done by setting the flue handle in...

Page 11: ...tant For delivery the door is locked in transit and it must be released before installation This is done by removing the two transport screws in the counterweights on the back of the stove TRANSPORT S...

Page 12: ...flective insulation panel must be installed to cover the flue collar up to the insulated chimney pipe The reflective insulation panel is included and is found screwed onto the back of fire place inser...

Page 13: ...d the two cut out easy bend flanges 90 see photo below Loosen the two labelled screws one on each side Place the two bottom holes on the reflective insulation panel over the two screws on the back of...

Page 14: ...inspector During testing the fireplace insert is installed in a cabinet made of non flammable 50 mm calcium silicate panels Skamotec 225 The stove comes with a flue collar that is 200 mm in diameter...

Page 15: ...EN EN 14...

Page 16: ...must never be tightly inserted into a cavity as steel expands when heated There must be a minimum convection air intake of 400 cm underneath the stove and 600 cm above it The minimum convection air ar...

Page 17: ...EN 16 SET UP The insulated chimney must extend all the way down to the flue outlet adapter To guide the hot air out of the convec tion grates a non flammable plate must be installed just over the grat...

Page 18: ...rniture 650 Interior distance to cabinet 50 Distance from vertical frame to flammable wall 100 If the insulation value is complied with greater than 0 03 m x K W the cabinet may be installed against a...

Page 19: ...ce insert is installed so that the vertical built in frame is flush against the wall the first 100 mm of the wall must be made of non combustible material such as 50 mm Skamotec 225 or brick INSTALLAT...

Page 20: ...EN 19 EN HEAT DISTRIBUTOR HEAT DISTRIBUTOR By installing a heat distributor unit above the fireplace insert heat can be transported to other rooms...

Page 21: ...flexi hose metal EXTERNAL AIR CONNECTION AIRSYSTEM All RAIS ATTIKA fireplace inserts can have an external air connection for combustion We call this external air supply AirSystem The system can be co...

Page 22: ...ins to crumble The liner panels are easy to place in position in the fireplace insert and can easily be replaced by you or your dealer Procedure for removing the combustion chamber lining 1 Remove the...

Page 23: ...ion chamber lining A steel baffle is positioned between the two convection ducts above the flue panel The steel baffle is held in place by two guide pins Remove the steel baffle by pushing the front e...

Page 24: ...n the upper locking pawl which is located above the door is released by turning it to the right on the right side and left on the left side The door is lifted so that the lower locking pawl is just fr...

Page 25: ...nderneath the grate can be removed and emptied in a non combustible container until it has cooled off Ash can be disposed of as ordinary household waste REMEMBER Never remove all the ash from the comb...

Page 26: ...or the counterweight cover Transport safety fitting 2 Remove the counterweight cover by pulling it up Counterweight cover 3 Loosen the locking ring 2 5 mm hex key Remove the number of counterweights t...

Page 27: ...s 1 Remove the side Skamol panel 2 Remove the access panel 3 Loosen the locking ring 2 5 mm hex key Remove the number of counterweights that allow the door to close slowly and at a constant speed Doub...

Page 28: ...EN 27 EN DECLARATION OF PERFORMANCE DECLARATION OF PERFORMANCE...

Page 29: ...ter NS 3058 2 12 g kg t rstof middelv rdi krav 4 Partikler efter NS 3058 2 12 g kg t rstof maksimalt krav 8 OGC efter CEN TS 15883 57 mgC Nm ved 13 O2 krav 120 St v efter FprEN 16510 1 23 mg Nm ved 13...

Page 30: ...EN 29 EN...

Page 31: ...EN EN 30...

Page 32: ...RAIS A S Industrivej 20 DK 9900 Frederikshavn Denmark www rais dk ATTIKA FEUER AG Brunnmatt 16 CH 6330 Cham Switzerland www attika ch...

Reviews: