Rain Bird PRS-DIAL Installation And Operation Manual Download Page 2

English

PRS-DIAL Pressure Regulating Module

Thank you for purchasing a Rain Bird 
PRS-DIAL pressure regulating module to 
optimize the performance of your irrigation 
system. This product automatically 
maintains constant outlet pressure 
regardless of inlet pressure fluctuations. 

Proper operation requires inlet pressure 
to be a minimum of 15 psi (1 bar) higher 
than desired outlet pressure. This product 
is designed for use with Rain Bird PGA, PEB, 
PESB, PESB-R, EFB-CP and BPES commercial 
valves. Much of the installation is done by 
hand; elsewhere, an adjustable wrench and 
pressure hose gauge are required.

As with all pressure regulators, this 
product senses back pressure before 
regulating outlet pressure. When opening 
the valve, it is normal for outlet pressure 
to momentarily exceed the desired set 
pressure and then begin regulating outlet 
pressure. This situation can be greatly 
reduced by following the installation and 
adjustment procedures below.

Notes:

1. For areas with very high pressure or 

uneven terrain, install sprinklers with  
PRS pressure regulating stems or  
SAM check valves.

2. When inlet pressures exceed 100 psi  

(6,9 bars), a pressure regulating master valve 
or inline pressure regulator is suggested.

3. Rain Bird does not recommend using 

the PRS-DIAL module for applications 
outside the recommended flow ranges 
(listed in Table 1).

Installation 

Refer to Figure 1.

1. Turn off water supply to the valve and 

turn flow control handle 

A

 clockwise 

until closed.

2. Remove solenoid 

B

 and adapter 

C

 

from bonnet 

F

 with an adjustable 

wrench.

3. Remove the Schrader valve cap 

D

.

4. Thread PRS-DIAL housing 

E

 into valve 

bonnet 

F

 until hand tight.

5. Loosen slightly to align latch 

G

 between 

ribs on plastic valves 

H

 or hole on brass 

valves, then push down latch to snap in place.

6. Thread PRS-DIAL cartridge 

I

 into 

housing until hand tight, then thread 
adapter and solenoid into top of housing.

7. Keep the flow control handle closed, 

then turn on water supply to the valve 
and proceed with adjustment.

Troubleshooting

External Leaks.

 Main cause is improper 

o-ring seal between bonnet, cartridge, 
adapter or solenoid.
1. Turn off water supply to the valve, then 

unthread parts at the leak.

2. Wipe or blow parts clean, reassemble, 

then turn on water supply and verify 
proper function.

Internal Leaks.

 Main cause is loose 

solenoid. If tightening solenoid does not  
fix the leak, proceed as follows:
1. Turn off water supply to the valve, then 

remove solenoid and clean debris.

2. Unthread the PRS-DIAL and check the 

rubber boot under the housing for tears 
or debris.

3. Check inside the solenoid bowl for 

damage to the white seat; a slight 
impression on top is normal.

4. Clean all parts and reassemble,  

then turn on water supply and verify 
proper function.

Excess Vibration.

 Main cause is excess 

air in the line or operation outside 
recommended flow ranges (see Table 1).  
To purge the air, proceed as follows:
1. Keep water supply on.
2. PGA VALVES ONLY: remove solenoid and 

let water flow for two minutes.

3. ALL OTHER VALVES: remove external 

bleed screw and let water flow for  
two minutes.

4. Open and close flow control handle a 

few times to remove air trapped inside 
the bonnet.

5. Reinstall parts, follow adjustment 

procedures and verify proper function.

Schrader Valve. 

Main cause of failure is 

loose valve stem or seal failure causing 
external leaking. 
1. Check torque of valve stem and verify 

that it is set at 3-5 in-lbs (0,3-0,6 Nm). 
Turn clockwise until tight and proper 
torque is achieved.

2. If the valve is still leaking, replace valve 

stem and turn clockwise until tight and 
proper torque is achieved.

Adjustment 

Refer to Figure 1.

1. Remove the PRS-DIAL cap by pulling 

away from the housing. Verify setting  
is 100 psi (6,9 bars).

2. Attach pressure hose gauge to  

Schrader valve 

D

.

3. Turn solenoid counter-clockwise  

1/4 turn to manually open the valve  
or activate the solenoid from the  
controller. Do not use external bleed.

4. Turn flow control handle 

counter-clockwise until pressure gauge 
indicates 15 psi (1 bar) above desired 
downstream pressure.

5. Turn PRS-DIAL adjustment knob 

J

 

until pressure gauge indicates the 
desired outlet pressure, then replace 
PRS-DIAL and Schrader valve caps.

6. Turn solenoid clockwise to close the  

valve or deactivate the solenoid from  
the controller.

Figure 1

Reviews: