3.4.2 Install Station Module
Install the station module that was included with your LXME2 controller in Slot 1.
NOTE:
To remove a module, press in on the (two) release buttons on either side of a module.
3.4.3 Dynamic Station Numbering
Next
Done
Back
SM12
SM12
SM12
SM12
01
1
2
3
4
12
25
36
37
48
13
24
AC
AL
BG
BP
Module change detected.
MODULE SETTINGS
Attach label with the matching letter
pair to each module. Press Next to
review Label References.
A Module Configuration screen is displayed whenever the LXME2 Controller detects a change in
module configuration. The Module Summary screen displays the module type detected in each
module slot along with the station numbers. With the Module Labels screen displayed. Locate the
Module Station Numbering Labels that are provided on a separate foldout sheet.
The Module Station Numbering Screen displays a pair of letters (example: Slot 1 = Label AC) for
each installed module. Find the station numbering label on the foldout sheet with the matching
letter pair and place it over the blue strip on the module. This label shows which station number
each terminal block is mapped to.
NOTE:
The Module Status can be reviewed at any time by turning the dial to the Station/MV
Settings dial position and selecting Module Status.
3.5 Connect Valve Wires
1.
Locate (or remove) the large knockout on the bottom of the controller cabinet.
2.
Attach a conduit fitting to the bottom of the cabinet; then attach conduit to the fitting.
3.
Feed the field wires through the conduit and into the controller cabinet.
4.
Strip the wire jacket back by a maximum of 1/2 inch (12 mm) and
connect each valve wire to
one of the numbered terminals on a station module.
5.
Field wires for valves are connected to module terminals using screw terminal blocks,
loosen the screws of the appropriate terminal using a Philips screw driver.
6.
Insert the wire. Then tighten the screw to clamp the wire in place.
7.
Connect the common wire(s) to any one of the COM terminals on the controller. Wires used
to connect the valves must be code approved for underground installation.
8.
(Optional)
Connect the master valve or pump start relay wiring to the MV and COM terminals.
9.
Once wiring is completed, fill top of conduit with waterproof caulking to prevent insect
intrusion into the controller cabinet.
3.5.1 Complete Installation
1.
Install the Front Door
by lining up the three door hinges with the plastic posts on the
controller. Press the hinges onto the posts until the front door snaps into place.
2.
Turn the programming dial to Diagnostics and select Test All Stations.
The Test All Stations
screen appears.
3.
Press the + and – buttons to add time to the Test Time (adjustable from 1 to 10 minutes) per
station; then press Run. A confirmation screen appears. Once Run is pressed, stations can be
monitored and advanced by turning the dial to the AUTO position and using the Adv button.
5