background image

Rain Bird 

Flow Sensors 

Manual

 

 

10 

 

 

Troubleshooting 

1) 

Using a voltmeter on the 0-20 VDC scale, connect the voltmeter across the sensor wires which are 
connected to the sensor input on the barrier strip. The voltage reading should be 8 VDC +/

– 0.5 V with no 

flow in the pipe. If the reading is in range, go to step 2. If not, go to step 3.

 

 

2) 

With the sensor installed in the pipe and flow through the pipe, connect the volt meter across the sensor 
wires at the sensor input of the barrier strip. The voltage should fall between 4 VDC and 8 VDC. The 
higher the flow rate, the lower the DC voltage level should drop. It should not drop below 4 VDC as your 
meter averages the DC level of the square wave signal generated by the sensor.

 

 

If this is correct, the flow sensor should be operational, and the flow monitor should display a flow rate or 
the transmitter output should change with a change in flow at the sensor. The signal generated by the 
sensor is a square wave with 5 msec pulses up to 100 Hz (at which time the pulses narrow to a 50% duty 
cycle), the use of an oscilloscope on the 5 msec time base, 2 VDC/division would indicate that the sensor 
is operating properly.

 

 

3) 

If the voltage at the sensor input is less than 7 VDC in a No Flow situation or less than 3 VDC in a flow 
situation, disconnect the sensor from the barrier strip and measure the voltage at the sensor input 
terminals of the barrier strip again. It should be between 8 VDC and 12 VDC. If the voltage is between 8-
12 VDC, the sensor is bad. If the voltage at the sensor input is still below 7 VDC or 3 VDC, the problem 
may be with the monitor.

 

 

4) 

If you suspect that the sensor is bad, you can test the monitor circuitry by connecting a piece of wire to 
one of the sensor input terminals and tap the other side of the wire to the other sensor input terminal. 
Shorting across the sensor input terminals ON and OFF repeatedly allows the display to respond by trying 
to calculate a flow rate for the frequency of your shorting action. If the display does not show a change 
from 0.00, it indicates a problem with the monitor.

 

 

5) 

If the flow sensor wiring is shorted or grounded the blue light on the module may blink continuously. 
Disconnect the flow sensor wire from the module in the controller. Remove and reinstall the module and 
the flow rate should return to zero. If secondary surge protection was installed remove it. Check sensor 
wiring for: 1) damaged insulation; 2) wire nuts must be direct burial type Rain Bird DBRY20 or 3M 
DBR/Y-6; and 3) sensor should be connected on dedicated PE-39 cable with no other signals in the 
cable. Fix the wiring and test the system. 

Summary of Contents for FS050P

Page 1: ...wept impeller shape provides higher more constant torque than other impeller designs and is less prone to fouling by water borne debris The forward curved shape coupled with the absence of magnetic dr...

Page 2: ...nics package inserted into a proprietary cast bronze pipe tee with threaded NPT female iron pipe thread FIPT connections They are available in the following sizes and thread types Model Thread Size FS...

Page 3: ...ertical pipes 3 Small pipe PVC and Bronze Tee Type sensors are Factory Set but for insert sensors the Insertion depth should be set to 1 1 2 for accurate flow readings The following pages show methods...

Page 4: ...tlet tee the inside dimension of the tee is not the same as the pipe O D Install the 2 NPT adapter provided using a thread sealant to prevent leakage Tighten as necessary Rain Bird insert style sensor...

Page 5: ...n data transmission to connect the sensor to the transmitter monitor or controller 3 Make a water tight splice Direct burial silicone grease splices are recommended Rain Bird DBRY20 or 3M DBR Y 6 Two...

Page 6: ...000 5 4 to 54 20 to 200 1 2 to 12 FS075P 3 4 PVC Tee Flow Sensor 0 1563 0 9000 3 3 to 33 13 to 125 75 to 7 5 FS050P 1 2 PVC Tee Flow Sensor 0 0780 0 9000 1 9 to 19 7 to 70 43 to 4 3 Description of Col...

Page 7: ...80 2 500 Sch 20 8 625 8 125 41 653 0 283 80 2 500 Sch 30 8 625 8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80...

Page 8: ...h 30 20 00 19 000 239 666 0 547 400 12 000 Sch 80 20 00 17 938 213 14 0 511 400 12 000 22 Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sc...

Page 9: ...necessary 7 Refer to Figure 3 To reinstall position the impeller in the cavity oriented as in Step 4 so that the impeller blades point into the flow direction and toward the small alignment hole locat...

Page 10: ...7 VDC in a No Flow situation or less than 3 VDC in a flow situation disconnect the sensor from the barrier strip and measure the voltage at the sensor input terminals of the barrier strip again It sh...

Page 11: ...r recommended design flow range for FS100B Linearity 0 2 of full scale over recommended design flow range 0 7 of full scale over recommended design flow range for FS100B Transducer Excitation Typicall...

Reviews: