Ec Controller
SYMPTOM
POSSIBLE CAUSE
CORRECTION
Program does not begin watering
as scheduled.
5. Programming dial is set to the
OFF position.
Set the programming dial to AUTO.
6. Start time has not been
properly entered for the
program.
Turn the dial to PRGM START TIME and
check the start times entered for the
program. If the start time is missing or
incorrect, enter it as described on p. 16.
7. Today may not be set as a
watering day for the program.
If today is a watering day for a program, the
program letter appears in the display. Turn
the dial to WATER DAY to check the
watering days for the program. If necessary,
set watering days as described on p. 15.
8. Water supply may be shut off.
Make sure water supply line has pressure.
A particular station does not
come on as scheduled.
9. No run time has been set for
the station.
Turn the programming dial to STATION RUN
TIME to check the run times set for the
station. To add a run time, see p. 17.
10. A short circuit in the solenoid
or valve wiring has disabled
the station.
Identify and repair the fault in the electrical
circuit.