background image

7

Ventilation of the room will of course alter the situation significantly but it should be
remembered that if the ventilator is not at ceiling level, a dangerous concentration can still
occur between the top of the ventilator and the ceiling.

For heavier than air gases such as propane or butane, the formation of dangerous layers
occurs at ground level. These gases tend to behave like water and will run down gradients
and pool at the lowest point.

The number of heads required in individual rooms is determined by the number of possible
hazards in the vicinity.

Gas leakage may occur around valves, flanges and anywhere where gas pipes are jointed.
It may be possible to cover several probable gas leaks in one room by the careful siting of
a single head. Cable ducts, trenches and manholes are also likely places where a build up
of heavy gases may collect.

When siting a head in such places it is most important to ensure that there is no likelihood
of flooding by water, or excessive dust which may block the sintered disc and prevent gas
reaching the sensor.

When monitoring gases outside, those lighter than air will be quickly dispersed, but gases
heavier than air will tend to form in layers and again cause a dangerous hazard. When
siting heads outside prevailing winds must be taken into consideration and adequate
protection given against wind and rain.

POISONING OF CATALYTIC SENSORS

Catalytic elements used in flammable gas sensors are liable to be rendered inactive due to
ʻpoisoningʼ by certain groups of compounds.

In general contact with any gaseous compound capable of producing an involatile residue
upon heating is to be avoided.

Examples of such substances are:

a. Silicon containing vapours, as emitted by silicone polishes, greases and oils.

b. Petroleum vapours containing tetra-ethyl lead or other organo-metallic compounds.

c. Phosphorus in the form of phosphate esters.

These compounds will permanently affect the detector and if their presence is suspected
the response of the detector should be determined by the calibration procedure.

It is also possible that the reaction of the detector to a flammable gas could be inhibited by
halogen containing gases such as chloroform, carbon tetra chloride and trichloro-ethylene.
this effect is not permanent.

Summary of Contents for FMC-40

Page 1: ...FMC 40 OPERATING HANDBOOK Manual No AWK043 4 C922...

Page 2: ...il and Field Terminals 15 3 Alarm Board Component Layout 16 4 Sensor Termination 17 SYSTEM DATA Manufacture date Works Order No Sensor type life life life life Gas Range Low alarm trip High alarm trip...

Page 3: ...is indicated by the amber L E D press again to continue the auto step sequence RANGE INDICATORS Three range indicators are positioned directly above the panel meter L E L Lower Explosive Level PPM Par...

Page 4: ...ER used to adjust the meter indication to read correctly when the sensor is subject to a test gas of known concentration ALARM SET SWITCH alarm trip points setting SENSOR CURRENT POTENTIOMETER sensor...

Page 5: ...core 1 5mm screened cable mineral insulated copper sheathed or steel wire armoured maximum cable loop resistance 20 ohms Transmitter 3 core 0 5 mm minimum screened cable mineral insulated copper shea...

Page 6: ...f the power supply to which the instrument will be connected SITING THE SENSING HEADS A key feature of the installation is the correct siting of the sensing head Several considerations must be taken i...

Page 7: ...vent gas reaching the sensor When monitoring gases outside those lighter than air will be quickly dispersed but gases heavier than air will tend to form in layers and again cause a dangerous hazard Wh...

Page 8: ...minutes for the sensors to stabilise Select channel 1 and for flammable or toxic sensors adjust meter to read zero by means of appropriate ZERO POTENTIOMETER marked Z on the alarm module or for oxyge...

Page 9: ...isplay toxic flammable or 20 8 for oxygen and press alarm set switch alarm indicators will turn off and the green power indicator will turn on SENSOR SUPPLY ADJUSTMENT CATALYTIC SENSOR Factory set no...

Page 10: ...servicing and instructed not to attempt to exceed the scope of such training Liaison should be established with those responsible for maintenance of the building fabric or redecoration etc to ensure t...

Page 11: ...switch on or off any electrical lights or appliances D Turn off the gas supply at the gas emergency control and or with L P G supply the storage tank E Open doors and windows to increase ventilation I...

Page 12: ...er Million vol Volume Hi High Alarm Lo Low Alarm C1 C4 Channel Selection Sensor F Fault Indicator P Power On Green Mains Fail Red Hold Channel Selection Reset Sounder Alarms Test Electronic System Tes...

Page 13: ...ly energised Normally de energised J3 Common Low Relay Normally energised Normally de energised J1 Common Fault Relay Normally energised Normally de energised J5 Sounder Permanent Mute JP10 remove Sta...

Page 14: ...secs T2 30 secs When used with GDS300 Flow sample systems FS Sensor Selection 24v 4 20mA input P Pellistor mV input 4 20mA Output TP3 TP4 Calibration TP1 TP2 Adjustments Potentiometer RV1 Sensor Zero...

Page 15: ...l Unit Detector Head mV pellistors or 3 wire CV W Y P W Y SIG P E Gas Detector Control Unit CV Transmitter Gas Detector Control Unit Transmitter W Y P 24V OV SIG Sensor Sensor Sensor RED ident R flamm...

Page 16: ...16...

Reviews: