24
FLo
Offset added or
subtracted to the
actual setting
temperature, to
define the value
of the lower floor
limitation.
Only effective if
the parameter
02
is adjusted on
(
FL.2
)
Example:
Comfort (Day)
setting: 20°C
Reduced (Night)
setting: 18°C
Floor limitation
offset: -1°C
Default:
0°C
Adjustable: From - 5°C
to + 5°C
Example:
Value of the lower
limitation during the
day: 19°C
Value of the lower
limitation during the
Night: 17°C
06
FL:Hi
Upper limit of the
floor temperature.
Only effective if
the external
sensor is
connected and
selected. (
FL.1
)
Default:
35°C
Adjustable: From ”
FLl
”
to 45°C
FLs
Setting
temperature for
the floor.
Only effective if
the parameter
02
is adjusted on
(
Cb.1
and
Cb.2
)
Default:
28°C
Adjustable: From 5°C
to 45°C
07
- - : - -
Selection of the
Time clock unit
24H
(24:00)
12H
(12:00 AM /PM)
08
DSt
Daylight Summer
time change
Summer<-
>Winter
YES:
automatic
change according to
date.
no:
no daylight
summer time
automatic change.
09
Uers
Software version
10
End
Press
(OK)
on this parameter to exit the
parameters menu end come back to the
main display.