D9210B Access Control Interface

Program Entry Guide

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for D9210B

Page 1: ...32207C 3 97 1997 Radionics D9210B Access Control Interface Program Entry Guide www PDF Zoo com firealarmresources com ...

Page 2: ...r to programming the device Each programming section program item and its page number are listed in the table of contents on the following page Throughout this manual programming prompts are shown in bold italic letters when they are used in a sentence For example Door is the first programming prompt in the DOOR PROFILE section of the program Reference to handlers modules categories and sections o...

Page 3: ...4 D Door Point 5 D Interlock Point 5 D Auto Door 5 D Fire Unlock 6 D DisarmOn Open 6 STRIKE PROFILE 7 Door 7 D Strike Time 7 D Shunt Time 7 D Buzz Time 7 D Extend Time 8 D Deact On Open 8 D RTEShunt Only 8 D REXShunt Only 9 EVENT PROFILE 10 Door 10 D Access Granted 10 D No Entry 10 D Enter Request 11 D Exit Request 11 www PDF Zoo com firealarmresources com ...

Page 4: ... door controller to which the reader will allow access Blank Door controller will not function NOTE All SDI devices regardless of area assigned will report to Area 1 Account 1 by default upon SDI failure If a D9210B becomes disconnected an SDI Fail and a MISSING POINT event will be created Programming Tip 9210 NOT READY will appear at this command center when you press the ENTER key if the D9210B ...

Page 5: ...one interlock point prevent multiple controllers from activating 1 127 129 247 The point number assigned to the interlock point Points 128 and 248 are reserved by the panel for internal use Blank There is no point number assigned to the interlock point Programming Tip CAUTION The interlock point will be considered in a normal state if it is bypassed swinger bypassed or forced armed This will resul...

Page 6: ...lly upon a Fire Alarm No Door will remain in its current mode upon a Fire Alarm Warning This will unlock the door regardless of the armed state D DisarmOn Open Default No Selections Yes or No Use this program item to determine whether the door needs to be physically opened prior to disarming the area upon a valid access request The user initiating the access request must have access levels that al...

Page 7: ...s door 1 240 The strike will activate for the amount of time programmed D Shunt Time Default 10 Selections Blank 1 240 seconds Enter the amount of time that the door point will be shunted to allow a user to open the door without causing the point to go into Trouble Alarm or a faulted condition Blank Shunt Time is not programmed for this door 1 240 The shunt will activate for the amount of time pro...

Page 8: ... access granted request No Strike will remain activated for the amount of the programmed strike time whether door is opened or closed Programming Tip In order for this function to work a point needs to be assigned to the door TO REDUCE FALSE ALARMS We recommend that you maintain this programming item as defaulted YES This will help prevent the door from bouncing open and causing a false alarm D RT...

Page 9: ...t an area Yes Programmed shunt time will activate so door can be manually opened No Request to Exit REX automatically activates the programmed strike and shunt time Application Tip Use this parameter when a user can open a door manually without relying on a token card to activate the strike such as with a push bar NOTE When REXShunt Only is Yes Request To Exit events are not logged reported or pri...

Page 10: ...n be initiated by a valid user ID valid door state changed at the command center automatically scheduled or armed state changes that hold a door open request to enter exit RTE REX Yes Access events from this door controller will be sent to the panel for processing No Access events from this door controller will not be sent to the panel for processing D No Entry Default No Selections Yes or No This...

Page 11: ... controller is not sent to the panel for processing Programming Tip RTE events require D Access Granted to be programmed YES D Exit Request Default No Selections Yes or No This program item determines if Request to Exit REX events are sent to the panel for processing memory printing and remote reporting Yes A DOOR REQUEST TO EXIT event from this door controller is sent to the panel for processing ...

Page 12: ...firealarmresources com ...

Page 13: ...e Radionics logo is a registered trademark of Radionics 1997 Radionics Inc Salinas CA USA All rights reserved Radionics Inc PO Box 80012 Salinas California 93901 0012 www PDF Zoo com firealarmresources com ...