Step 6: Request to Enter (RTE), Terminals 11 and 12
Description. When terminal 11 is momentarily shorted to terminal 12, the strike
is activated and the door point is shunted.
Shunt Only: An option is provided that only shunts the point when this input is
momentarily shorted. To activate the shunt, but not the strike, program RTE
Shunt Only? as YES.
Step 7: Request to Exit (REX), Terminals 13 and 12
Description. When terminal 13 is momentarily shorted to terminal 12, the strike
is activated and the door point is shunted.
Shunt Only: An option is provided that only shunts the point when this input is
momentarily shorted. To activate the shunt, but not the strike, program REX
Shunt Only? as YES.
IMPORTANT: REX must not be used for emergency exit applications. NFPA 101
requires that a UL listed panic device be used to provide direct power from the
standby power source. (see Figure 2 for wiring an emergency exit device).
Check with your local Authority Having Jurisdiction (AHJ) prior to installing your
system.
Step 8: Enclosure Tamper Switch, Terminals 8 and 9
Description. A short to this loop will generate a Missing Trouble Point ### for
the point number assigned to the D9210B. With this tamper point faulted, the
D9210B will still function.
Connect a N/O tamper switch to terminals 8 and 9. Upon opening the enclosure,
the tamper switch will short the inputs and generate the Missing Trouble Point
message.
TROUBLESHOOTING TIP:
SDI FAILURE ###
and
MISSING PT ###
are
reported to the central station when the SDI bus has failed or the D9210B is
missing.