D9000/D7000 Series Installation and Troubleshooting Quick Reference

Page  8

33317D  4/97

Phone Line Trouble

Phone line problems can result in the panel going into Communications Failure.

Symptom

Diagnosis

Remedy

SERVC PH LINE #1
(or 2 if two lines are
used) appears in
command center
display.

D9412/D9112 phone
line monitor detects a
phone line as faulted.

1.

Verify that the telephone cord is correctly
connected to the RJ31X and the panel.

2.

Verify the Ground Start Jumper is in the
correct position.

3.

If using a ground start phone line, verify
D136 relay is in socket K6/J5.

4.

Verify that the RJ31X jack is wired
correctly. The incoming phone line must
be wired to terminals 4 and 5. The in-
house phone system must be wired to
terminals 1 and 8.

5.

Verify that all telephones are on-hook.
Leaving a telephone on hold after the
other party hangs up creates an off-hook
condition. Verify that no phones are on
hold.

If completing the steps above does not
restore the phone line, meter the phone lines.
You should meter 4.5 to 7.5 VDC when the
line is idle (on-hook). You should meter 8 to
13 mA of current when the line is active (off-
hook). If your readings are below the
minimum values, contact your telephone
company repair service.

Communications Failure

Follow the 

Phone Line Trouble  procedure to verify that there is no problem with the phone

lines at the installation. If the phone lines are good, monitor the lines (preferably at the
receiver) for the symptoms listed below.

Symptom

Diagnosis

Remedy

Panel does not
connect to central
station.

The D136 relay in J10
for ground start phone
systems is inserted
incorrectly.

Insert the D136 relay in socket J10
correctly. Also check that phone line is
connected and that phone jack is wired
properly. See the 

Relays section of this

manual for instructions.

The receiver
answers the call
and provides an
initial “handshake”
acknowledgment,
but does not
acknowledge the
D9412’s report
transmission with
a “kiss-off”
acknowledgment .

The receiver is not
compatible with the
D9412/D9112
transmission format.

Verify that the receiver is compatible
with the format the D9412 is using
(either BFSK or Radionics Modem
IIIa

2

™ Communications Format). See

Phone in the D9412/D9112 Program
Entry Guide (74-07695-000).

D9412/D9112 requires D6500 MPU and
Line Card EPROM revision 8.00 or
higher.

Noisy phone lines are
interfering with report
transmission.

Try making a voice call to the receiver
on the line to verify the noisy condition.
It may be necessary to have the phone
company check the lines.

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for D9000 Series

Page 1: ...icator 12 D7212Control Communicator 13 QuickReferenceTerminalDescription 14 Introduction This reference contains the very basic information a trained installer needs to install and troubleshoot a D900...

Page 2: ...oint tested for 60 seconds After 60 seconds the display returns to the points to test message Extra Points display default text If you incorrectly set the switches on a POPIT to a point number that is...

Page 3: ...NTESTED N EXT SERVICE WALK 246 PTS TO TEST 245 PTS TO TEST 244 PTS TO TEST POINT TEXT POINT TEXT POINT TEXT 1 PTS TO TEST 0 PTS TO TEST IDLE TEXT POINT TEXT Test a device Text displays 60 seconds Test...

Page 4: ...d at the last address on the ZONEX bus Install a D8125 POPEX and D9127 POPITs for points 121 127 on ZONEX 1 and for points 241 247 on ZONEX 2 Sensor loop switch 1 to 8 is turned off on OctoPOPIT If th...

Page 5: ...res input from all points in the same area programmed for sensor reset during sensor reset Two points are programmed with the same address Points programmed with the same address do not function corre...

Page 6: ...d 24 share a common circuit breaker Check wiring and devices connected to these terminals for shorts or grounds If only one POPEX module is connected to the panel POPEX module may be incorrectly conne...

Page 7: ...programmer connector J7 3 Check each conductor in the data power cord for continuity AC induction through the on board point sensor loops the DATA BUS or the ZONEX BUS 1 Verify a proper earth ground a...

Page 8: ...contact your telephone company repair service Communications Failure Follow the Phone Line Trouble procedure to verify that there is no problem with the phone lines at the installation If the phone li...

Page 9: ...s Can hear ring with test set at receiver location Line card in receiver may be faulty Review receiver manuals for trouble shooting procedures The D9412 D9112 reaches a busy signal for all ten attempt...

Page 10: ...r t 0 0 1 3V DC PER IPH ERAL DE VICE W IR ING Z ONE X O UT 1 ZO NEX IN 1 Z ONE X O UT 2 ZO NEX IN 2 ZON EX P OWE R Z ONE X CO MM ON O p eratio n Mo nito r Puls es W he n No rma l F licke rs W h e n Ri...

Page 11: ...UT 1 ZO NEX IN 1 ZO NE X O UT 2 ZO NEX IN 2 ZO NEX POW ER Z ON EX CO MMO N O p e ra tion M o n itor P uls es W he n N o rm al Fli cke rs W h en R ing ing PROG CONN RED YELLOW G RE EN B LA CK 1 7 0 58...

Page 12: ...ZO NEX IN 2 ZO NEX PO WE R Z O NEX CO MMO N O p era tio n M o nit or P uls es W he n No rm al Fli cke rs W h e n R in gi ng PROG CONN RE D YELLO W GRE EN BLACK 1 7 058 23 0 02 3 2 PO W ER DATA BU S A...

Page 13: ...ON EX IN 2 Z ON EX PO WE R ZO NEX CO MMO N Op erati on Mo nit or Pu lse s W h en No rm al F lick er s W h en Rin gi ng PROG CONN RE D Y EL LO W GREEN BLA CK 17 05 82 3 0 02 3 2 PO W ER DATA BU S A CO...

Page 14: ...or alarm verification Shares circuit breaker with terminals 6 and 7 D136 Plug in Relay required Install a D136 in socket K1 for output at terminal 8 9 COMMON Terminal 9 is common for Auxiliary Power...

Reviews: