D9000/D7000 Series Installation and Troubleshooting Quick Reference
Page 7
33317D 4/97
Problems Programming the Panel
Before attempting to program the panel, you should be familiar with the basic operation of
the D5200 programmer. See the
D5200 Operation Manual (74-06176-000). If you still
experience problems, check for the symptoms below.
Symptom
Diagnosis
Remedy
The programmer
displays PLUG IN
D9412/D9112
when you press
SEND or RECV.
The programmer is
not correctly
connected to the
D9412/D9112.
1.
Verify that the data/power cord is plugged
into the COMMUNICATOR port on the
D5200.
2.
Verify that the data/power cord is plugged
securely into the D9412/D9112
programmer connector (J7).
3.
Check each conductor in the data/power
cord for continuity.
AC induction through
the on-board point
sensor loops, the
DATA BUS, or the
ZONEX BUS.
1.
Verify a proper earth ground at terminal
10.
2
Disconnect on-board point sensor loops,
the DATA BUS (terminals 30, 31), and the
ZONEX BUS (terminals 25, 26,27,28).
After plugging in
the programmer,
the panel
transmits SDI
trouble reports for
supervised SDI
devices
(command
centers, printer
interface modules,
etc.). All SDI
devices stop
operating.
You haven’t entered
the D9412/D9112
handler within 30
seconds of plugging in
the programmer.
Enter the D9412/D9112 handler within 30
seconds of plugging in the programmer.
Once the SDI reports are generated, sending
or receiving a handler or disconnecting the
programmer returns the SDI devices to
normal operation.